Diagnostics

Smart Relay Messages

Description

Here is detailed information on the error messages that are returned by the smart

 

relay, their possible causes and how to remedy the problem.

Error Messages The table below lists the error messages that a smart relay could return. These messages generally indicate incompatible actions requested by the user.

Message

Cause

Corrective action

 

 

 

 

 

 

The user has requested to access the

 

NO PARAMETER

PARAMETERS option when no parameter is

 

available (the diagram does not include any

 

 

 

 

 

 

elements with parameters).

 

 

 

 

 

TRANSF.ERR.

A transfer was in progress and the link with the

See the documentation for the

PC was unexpectedly interrupted.

programming software.

 

 

 

 

 

TRANSFER ERROR: NO

A transfer to the EEPROM was requested and the

Check the presence and correct

MEMORY

EEPROM is not present or incorrectly located.

location of the EEPROM.

 

 

 

 

 

 

The user has requested to transfer a program

Check the origin of the program to transfer

TRANSFER ERROR:

that does not match the characteristics of the

and choose a program that is compatible

CONFIG INCOMPAT

target smart relay, for example: Clock, analog

with the appropriate smart relay.

 

 

input, software version.

 

 

 

 

 

 

 

TRANSFER ERROR:

This error appears if one of the versions of the

 

smart relay does not correspond to: Firmware,

Check the firmware version used.

VERSION. INCOMPAT

LD or FBD functions

 

 

 

 

 

 

 

 

Outputs are displayed

One or more static outputs have shorted or

Troubleshoot, then stop the smart relay

to end the blinking before selecting

flashing on the main screen

overloaded.

RUN mode again (automatic reset).

 

 

 

 

 

 

 

 

 

 

 

188

SR2MAN01 11/2007

Page 168
Image 168