TRANSFER Menu

Backup Memory

Module Transfer

Procedure for transferring the application, from the backup memory to the smart relay, for a smart relay with LCD and keyboard:

Step Action

1Insert the EEPROM cartridge (SR2 MEM02) with the program to be transferred into the slot provided.

2Select the transfer type: MEMORY>ZELIO using the navigation keys .

3Confirm the transfer command with the Menu/OK key.

4Wait for the transfer to end.

Display: > > > MODULE then TRANSFER. OK when it is complete.

5Confirm again by pressing Menu/OK to exit the menu.

Result: the display returns to the INPUTS-OUTPUTS screen in RUN mode and to the MAIN menu in STOP mode.

Procedure for transferring the application, from the backup memory to the smart relay, for a smart relay without LCD or keyboard:

Step

Action

 

 

1

Since the smart relay is not powered-on, insert the EEPROM cartridge (SR2

 

MEM02) into the slot provided.

 

 

2

Power up the smart relay.

 

During the transfer, the LED display is off.

 

 

3

Wait for the transfer to end.

 

During the transfer, the LED display is off, then at the end of the transfer the LED flashes.

 

 

4

z If the flashing is slow (3 Hz), the transfer has been successful, the smart relay is in

 

RUN, remove the EEPROM cartridge (SR2 MEM02).

 

z If the flashing is rapid (5Hz), the transfer has failed due to incompatibility between the

 

configuration necessary for the program to be transferred and that of the smart relay.

 

 

Note: When the smart relay is in STOP mode, the LED display is lit and does not flash.