Schneider Electric SR2MAN01 user manual Module → Backup Memory Transfer, TRANSFER Menu

Models: SR2MAN01

1 177
Download 177 pages 48.3 Kb
Page 59
Image 59
TRANSFER Menu

TRANSFER Menu

Module

Backup Memory

Transfer

Note: if an application is already present in the backup memory, it will be overwritten by the new transfer (no test is performed to check the memory is free).

Note: It is not possible to directly transfer an application created with version V2 of the programming software from the SR2 MEM01 memory to the smart relay if this latter contains version V3 firmware.

In this case, see what action you should take in the section Program incompatible with firmware of the module (see Application incompatible with firmware on the smart relay, p. 70).

For more information about the compatibility of the memory cartridges, see Compatibility between the memory cartridges and the version of the firmware on the smart relay, p. 195.

Procedure for transferring the application, from the smart relay to the backup memory:

Step Action

1Insert the EEPROM cartridge (SR2 MEM02) into the slot provided.

2Select the transfer type: MEMORY>ZELIO using the navigation keys Module →Manual background .

3Confirm the transfer command with the Menu/OK key. (Enter the password if the program is password-protected).

4Wait for the transfer to end.

Display: > > > MEMORY then TRANSFER. OK when it is complete.

5Confirm again by pressing Menu/OK key to exit the menu.

Result: The display returns to the INPUTS-OUTPUTS screen in RUN mode and to the MAIN menu in STOP mode.

68

SR2MAN01 11/2007

Page 59