Schneider Electric SR2MAN01 user manual FBD mode Parameter Modification, Parameters in, RUN Mode

Models: SR2MAN01

1 177
Download 177 pages 48.3 Kb
Page 44
Image 44
FBD mode

PARAMETERS Menu

FBD mode

Parameter Modification

Functions with parameters in FBD mode:

zNumerical Constant-Type Inputs,

zClocks,

zGain,

zTimers: TIMER A/C, TIMER B/H, TIMER Li,

zCounters: PRESET COUNT,

zFast counter,

zCAM block.

To access the parameters of the FBD blocks, you must know end enter the block number. This number appears in the programming software on the wiring sheet at the top right corner of the block.

Only those functions used in the program and with parameters are listed in the PARAMETERS menu.

Parameter modification procedure:

Step Action

1Place the cursor over the PARAMETERS menu in the main menu (PARAMETERS flashing) and confirm by pressing the Menu/OK button.

Result: The parameters window opens to the first parameter.

2Select the function to modify.

To access the required function, scroll through the function block numbers (navigation keys Parameters in and RUN Mode ) until you reach the right one.

3Select the parameter to modify.

The z From the PARAMETERS (see PARAMETERS Menu, p. 51) menu, and Manual background keys are used to place the cursor over the parameter to modify.

4Modify the parameter using the + and - keys ( Manual background and Manual background ) of the contextual menu.

5Confirm the modifications by pressing Menu/OK, which will open the confirmation window.

6Confirm again twice by pressing Menu/OK to save.

Result: The display returns to the INPUTS-OUTPUTS screen in RUN mode and to the MAIN menu in STOP mode.

Parameters in

It is therefore possible to modify parameters in RUN mode dynamically as long as

RUN Mode

they are not locked.

 

The modifications can be made:

 

z From the PARAMETERS (see PARAMETERS Menu, p. 51) menu,

 

z From the MONITORING (see MONITORING Menu, p. 53) (LD) menu: Move the

 

pointer over the function to be modified using the navigation keys and open the

 

parameters window from the contextual menu (Shift key).

 

 

52

SR2MAN01 11/2007

Page 44
Image 44
Schneider Electric SR2MAN01 user manual FBD mode Parameter Modification, Parameters in, RUN Mode