zAbsence of backup memory

TRANSFER Menu

Possible Errors Below are the possible errors and, for each case, the messages that are displayed:

zAbsence of backup memory

Error message:

TRANSFER ERROR: NO MEMORY

zConfigurations of the hardware and program to transfer incompatible

Error message:

TRANSFER ERROR: CONFIG INCOMPAT (hardware or software reference numbers).

 

Refer to the DEFAULT Menu, p. 77 chapter to consult the error number and clear it.

 

 

 

 

Note: The transfer of one module program to another via a memory card is only

 

possible between smart relays with the same reference. For example, it is

 

impossible to transfer a program from a module with a clock to a module that does

 

not have one.

Application

 

 

 

 

If the application stored in backup memory SR2 MEM01 was created with a version

incompatible

of the programming software that is incompatible (see Compatibility between the

with firmware on

memory cartridges and the version of the firmware on the smart relay, p. 195) with

the smart relay

the firmware of the target smart relay, proceed as follows:

 

 

 

 

Step

Action

 

 

 

 

1

Load the application from the backup memory to a smart relay with compatible firmware.

 

 

Note: If no smart relay has firmware that is compatible with the application, use the

 

 

programming software version that was used to create the application to load

 

 

compatible firmware into the target smart relay:

 

 

 

 

2

Use the version of the programming software that was used to create the application

 

 

to load it from the smart relay toward the PC.

 

 

 

 

3

Save the application uploaded in step 2.

 

 

 

 

4

Launch the latest version of the programming software.

 

 

 

 

5

Open the application saved in step 3.

 

 

Result: The programming software converts the application.

 

 

 

 

6

Load the converted application and the associated firmware to the target smart relay.

 

 

 

 

 

 