Frequently

 

Here below are the most frequently asked questions and their answers:

Asked Questions

 

 

 

 

 

Question

Answer

 

 

 

 

 

 

 

Some parameters are not accessible. See the documentation to find

I cannot access some parameters.

out whether these elements can be changed. Example of an element

that cannot be changed: Counter function block counting direction.

 

 

 

 

 

 

This element is only accessible by wiring in a ladder diagram line.

 

 

 

 

 

 

 

To access the parameters, you must use the navigation keys and

I still cannot access some parameters.

to position the cursor above them. The and are used to

 

 

 

change these values. Then press Menu/OK to confirm the changes.

 

 

I cannot RUN my smart relay even though I

CAUTION, make sure that the error symbol (!) is not displayed in

enable the RUN/STOP option in the main menu

the contextual menu line. Correct the error in order to RUN the

using the Menu/OK key.

smart module.

 

 

I would like to change my diagram lines but the

Ensure that the smart relay is indeed stopped. Changes in RUN

Menu/OK key no longer works.

mode are not allowed.

 

 

When I try to change my diagram lines, the smart

Not necessarily, this situation may occur when 4 consecutive

relay shows me a screen with only line numbers

blank lines have been inserted at the start of the ladder diagram or

(LINE No.). Have I lost all my work?

between the command lines.

 

 

I have a ladder diagram that uses the Z key ( ,

 

, , ) for a pushbutton. I would like to test it

No this is impossible.

but when I display the diagram dynamically, my Z

 

key is no longer operational. Can I make it work?

 

 

 

I generated a ladder diagram on a smart relay

 

with a clock. Can I use a backup memory to

No this is impossible.

transfer it to a smart relay without clock?

 

 

 

When entering a ladder diagram, the clock

It is quite possible that the smart relay is one without a clock.

function blocks do not appear when choosing the

Consequently, the clock function blocks are not accessible. Check

contacts. Is this normal?

the product reference numbers.

 

 

When entering a ladder diagram, the analog

It is quite probable that the smart relay does not have analog

function blocks do not appear when choosing the

inputs. Consequently, the analog function blocks are not

contacts. Is this normal?

accessible. Check the product reference numbers.

 

 

 

 

 

 

 

 