CONFIGURATION Menu

FILTER Menu

Description

Filter-Type

Selection

This function is used to detect more quickly any changes in states of Discrete inputs.

Two choices are available:

z

Fast,

 

 

z

Slow.

 

 

Response time:

 

 

 

 

 

Filtering

Commutation

Response time

 

 

 

Slow

ON OFF

5 milliseconds

 

 

 

 

 

 

OFF ON

3 milliseconds

 

 

 

Fast

ON OFF

0.5 milliseconds

 

 

 

 

 

 

OFF ON

0.3 milliseconds

 

 

 

 

This selection can only be made when the smart relay is in STOP. By default, the smart relays are configured in SLOW.

Note: This function is available on smart relays with a direct voltage power supply.

Note: to return to the main menu from the CONFIGURATION menu, use the navigation key .

The current type is indicated by the selection symbol (black diamond).

Procedure for selection of filter type:

Step Action

1Select the type of filtering using the keys (the selection will flash).

2Confirm with Menu/OK.

Result: the display returns to the MAIN menu.