Module Summary Table, Continued
Module
Name Total
Available
in 7700
Used in
Factory
Config.
High-
Speed
Capable
Setup Registers Range or Options Creation Default
Volts Mode 4W-WYE, 3W-WYE,
DELTA, SINGLE or DEMO 4W-WYE
PT Prim 1 to 999999 120/277/ 347 (
dependson ordering option
)
PT Sec 1 to 999999 120/277/347 (
dependson ordering option
)
CT Prim 1 to 999999 5
CT Sec 1 to 999999 5
I4 CT Prim 1 to 999999 5
I4 CT Sec 1 to 999999 5
V1Polarity NORM AL or INVERTED NORMAL
V2Polarity NORM AL or INVERTED NORMAL
V3Polarity NORM AL or INVERTED NORMAL
I1Polarity NORMAL or INVERTED NORMAL
I2Polarity NORMAL or INVERTED NORMAL
I3Polarity NORMAL or INVERTED NORMAL
I4Polarity NORMAL or INVERTED NORMAL
PhaseOrder ABC or ACB ABC
Nom Freq
not configurable - factory ordering option
Power Meter * 3 3 1
Phase Lbls ABC, RST, XYZ, RYB or
123 ABC
Pulse Merge 8 1 8 EvLog Mo de LOG ON or LOG OFF LOG OFF
PulseWidth 0 to 2 x 106 seconds 1
OutputMode PULSE or KYZ PULSE
Polarity INVERTING or
NON-INVERTING INVERTING
Pulser 10 none none
Port The Port option is variable, and depends on the
options ordered with the 9700 Power Meter. There
is no default port; the available ports will be
presented when you enter this setup register.
Eval Mode Value, Percentage Value
Over Pickup 0 to 1x109 %0
Over Dropout 0 to 1x109 %0
Relative
Setpoint 10 5 none
Under Pickup 0 to 1x109 %0
* denotes Core module (refer to chapter 4)