Input Ratings, continued
20 mA AC/DC nominal full scale input (25 mA AC/DC max.)
Overload withstand: 35mA continuous, 70mA for 1 second non-recurring
Input Impedance 100Ω
Accuracy: AC: ±0.25% F.S.; DC: ±(0.25% F.S. + 0.1% per Vcm*) total erro r
0-20 mA
Option
Maximum Common Mode: 20 V
1.0 VAC/VDC nominal full scale input (1.25 VAC/VDC max.)
Overload withstand: 20 VAC/VDC continuous, 40 VAC/VDC for 1 second non-recurring
Input Impedance 49.9 kΩ
Accuracy: AC: 60.25% F.S. DC:6(0.25% F.S. + 0.13% per Vcm*) total error
Optional
Onboard
Analog
Inputs
continued
0-1 V Option
Maximum Common Mode: 12 V
10.0 VAC/VDC nominal full scale input (12.5 VAC/VDC max.)
Overload withstand: 20 VAC/VDC continuous, 40 VAC/VDC for 1 second non-recurring
Input Impedance 49.9 kΩ
Accuracy: AC: ±0.25% F.S.; DC: ±(0.25% F.S. + 0.025% per Vcm) total erro r
0-10 V Option
Maximum Common Mode: 25 V
Standard 85-240VAC (47-440 Hz) or 110-300VDC, 1 Amp worst case loading (56 W) @ 100 VAC @ 25°C
20-60VDC @ 30 W worst case
Power
Supply* -P24/ 48
option Power supply fuse current rating, type and rupturing speed: 3 A slow blow
* Power supply ratings apply to both 9700 Power Meter and the external output boards.