Ethernet COM
The Ethernet COM menu accesses the Ethernet module’s setup registers.
The Ethernet module controls the 10Base-T and 10Base-FL ports on the
optional XPRESS CARD.
Setup Register Function
Protocol Sets the communications protocol for the Ethernet ports.
IP Address Sets t h e I P Address for the 9700 Power Meter
Subnet Mask Used if subnetting applies to your network – see your Network
Administrator
Gateway Used in multiple network configurations – see your Network
Administrator
Typically your Network Administrator will provide you with the appropriate
IP Address for the 9700 Power Meter. The Subnet Mask and Gateway
settings are only required if you have communications between multiple
Ethernet networks, and if subnetting is implemented.
Demand
The Demand menu accesses some of the setup registers in the factory-
configured Sliding Window Demand and Thermal Demand modules. These
setup registers control the timing of demand calcula tions.
Setup Register (module) Function
Sub Intvl (Sliding Window) * The time, in seco n ds, in the sliding window demand sub-interval
# SubIntvls (Sliding Window) * The number of sub-intervals in the sliding windo w
Interval (Thermal) * The time, in seconds, in the thermal demand interval
* These setup registers are available for each demand module. T h e MGT displays SD1 to SD4 to
indicate Sliding Window Demand modules 1 through 4, and TD1 through TD4 to indicate
Thermal Demand modules 1 through 4.
Param eter ResetThe Parameter Reset menu allows you to reset various cumulative
parameters. To access Parameter Reset, press SETUP, PARAMETER RESET,
then use the up and down arrow keys to highlight the parameter you want
to reset. When the parameter you want is highlighted, press ENTER.
The first time you reset a parameter, the password screen appears – enter 0
(zero) or the user password you previously configured. The MGT displays
“…Done” next to the parameter name once it has been suc cessfully reset.
The parameters that are reset by each menu selection are detailed below.