DISPLAYING DATA 2-15
Harmonics Logging Framework

This portion of the factory configuration records voltage and current

harmonics measurements. Mean and average values are calculated,

recorded and then reset every 60 minutes.

Displayed/Accessible by Default
Description of
Parameter or Function WinPM MGT
Module
Name Module
Label Output
Register Label
Mean Phase A Voltage THD* lS W Demand #21 V1 THD* mean V1 THD* mean
Mean Phase B Voltage THD lS W Demand #22 V2 THD mean V2 THD mean
Mean Phase C Voltage THD lS W Demand #23 V3 THD mean V3 THD mean
Mean Phase A Current THD lS W Demand #24 I1 THD mean I1 THD mean
Mean Phase B Current THD lS W Demand #25 I2 THD mean I2 THD mean
Mean Phase C Current THD lS W Demand #26 I3 THD mean I3 THD mean
Mean Phase A Current K
Factor
lS W Demand #27 I1 K Fac mean I1 K Fac mean
Mean Phase B Current K
Factor
lS W Demand #28 I2 K Fac mean I2 K Fac mean
Mean Phase C Current K
Factor
lS W Demand #29 I3 K Fac mean I3 K Fac mean
High Phase A Voltage THD lMaximum #46 V1 THD* high V1 THD* high
High Phase B Voltage THD lMaximum #47 V2 THD high V2 THD high
High Phase C Voltage THD lMaximum #48 V3 THD high V3 THD high
High Phase A Current THD lMaximum #49 I1 THD high I1 THD high
High Phase B Current THD lMaximum #50 I2 THD high I2 THD high
High Phase C Current THD lMaximum #51 I3 THD high I3 THD high
High Phase A Current K
Factor
ll
Maximum #52 I1 K Fac high I1 K Fac high
High Phase B Current K
Factor
ll
Maximum #53 I2 K Fac high I2 K Fac high
High Phase C Current K
Factor
ll
Maximum #54 I3 K Fac high I3 K Fac high
Harmonics Logging trigger lPeriodic Timer #3 Harm Log Trg Harm Log Trg
Harmonics Logging enable lExternal Boolean #6 Harm Log Enble Harm Log Enble
High Harmonics reset lFeedback #3 Rset Harm high Rset Harm high
Mean Harmonics Recorder lData R ecorder #7 Harm mean Log Harm mean Log
High Harmonics Recorder lData Recorder #8 Harm high Log Harm high Log
* THD = Total Harmonic Distortion