Modbus Slave Module #3 Links

Measurement Label Source

Module Modbus Module and Input

Number Modbus

Register

Maximum Avg L-L Voltage Vll avg max M aximum Modbus Slave #3 – Source Input #1 40059-40060
Maximum Average Current I avg max Maximum M odbus Slave #3 – Source Input #2 40061-40062
Maximum Total kW kW tot max Maximum Modbus Slave #3 – Source Input #3 40063-40064
Maximum Total kVAR kVAR tot
max Maximum Modbus Slave #3 – Source Input #4 40065-40066
Maximum Total kVA kVA tot max Maximu m Modbus Slave #3 – Source Input #5 40067-40068
Maximum Line Frequency Freq max Maximum Modbus Slave #3 – Source Input #6 40069-40070
Minimum Avg L-L Voltage Vll avg min Minimum Modbus Slave #3 – Source Input #7 40071-40072
Minimum Average Current I avg min Minimum Modbus Slave #3 – Source Input #8 40073-40074
Minimum Line Frequency Freq min Minimum Modbus Slave #3 – Sourc e I n put #9 40075-40076
kW Sliding Window Demand kW swd Sliding Win Demand M odbus Slave #3 – Source Input #10 40077-40078
kVA Sliding Window
Demand kVA swd Sliding Win Demand Modbus Slave #3 – Source Input #11 40079-40080
kVAR Sliding Window
Demand kVAR swd Sliding Win Demand Modbus Slave #3 – Source Input #12 40081-40082
Maximum kW SW Demand kW swd
max Maximum Modbus Slave #3 – Source Input #13 40083-40084
Maximum kVA SW Demand kVA swd
max Maximum Modbus Slave #3 – Source Input #14 40085-40086
Maximum kVAR SW Demand kVAR td
max Maximum Modbus Slave #3 – Source Input #15 40087-40088