Normally Open, Solid State Relays
AC Outputs (Zero Voltage Turn
On) DC Outputs
Part Number GDOAC120 GDOAC240 GDODC60 GDODC200 GDODC6 0L
(Low Leakage)
Nominal Line Voltage: 120 VAC 240 VAC
N/A N/A N/A
Load Power Factor: 0.4 min. 0.4 min.
N/A N/A N/A
Frequency Range: 25 Hz to 70 Hz 25 Hz to 70 Hz
N/A N/A N/A
Maximum Line Voltage:
N/A N/A
60 VDC 200 VDC 60 VDC
Maximum Off-state Leakage
@ 60Hz (AC) or @ 60 VDC
(DC):
2 mA rms 4 mA rms 1.5 mA 0.01 mA 0.01 mA
Load Voltage Range: 24 to 140 VAC 24 to 280 VAC 3 to 60 VDC 4 to 200 VDC 3 to 60 VDC
On-state Voltage Drop: 1.5 Volts max. 1.5 Volts max. 1.2 Volts max. 1.75 Volts max. 1.2 Volts max.
Clamping Voltage: N/A N/A 80 VDC max. 360 VDC max. 80 VDC max.
Power Dissipation: 1.0 Watt/Amp
typ. 1.0 Watt/Amp
typ. 1.0 Watt/Amp
typ. 1.5 Watt/Amp
typ. 1.0 Watt/Amp
typ.
Load Current Range (RMS): 0.03 t o 3.5 A 0.03 to 3.5 A 0.02 to 3.5 A 0.02 to 1.0 A 0. 02 to 3.5 A
Turn-on Time: 8.3 msec max. @
60Hz 8.3 msec max.@
60Hz 20 µsec max. 75 µsec max. 75 µsec max.
Turn-off Time: 8.3 msec max. @
60Hz 8.3 msec max.@
60Hz 50 µsec max. 750 µsec max. 500 µsec max.
Surge Current (peak): 80 Amps @ 60
Hz, 1 cycle; 25
Amps @ 60 Hz,
60 cycles
80 Amps @ 60
Hz, 1 cycle; 25
Amps @ 60 Hz,
60 cycles
5 Amps
maximum for 1
second
5 Amps
maximum for 1
second
5 Amps
maximum for 1
second
Transient Power Dissipation:
N/A N/A
400 Watts @ 1 msec non-recurring
Optical Isolation
(Input to Output): 4000 VAC rms
Operating Temperature
Range: -40°C to +100°C
Storage Temperature Range: -40°C to +125°C
Standards and Certification: UL File # E58632, CSA File # LR38763
Transient Protection: Meets ANS I 37.90-1989 Surge Withstand Capability Test