Digital Input Dry Contact Modules
Part Number GDICC
Isolation, Input to Output 2500 VAC rms
Storage Temperature Range -40°C to 125 °C
Operating Temperature Range 0°C to 60°C
Maximum Dry Contact Voltage
Rating 25 VDC
Minimum Dry Contact Current
Rating 5 mA
Maximum Turn-on Time 3.0 msec
Minimum Turn-off Time 3.0 msec
Standards and Certification: UL File # E58632, CSA File # LR38763
Transient Protection: Meets ANSI 37.90-1989 Surge Withstand Capability
Test
Thermocouple Input ModulesThermocouple Type Type J Type K Type R Type T
Part Number GAITCJ GAITCK GAITCR GAITCT
Input Range 0 to 700°C -100 to 924°C 0 to 960°C -200 to 224°C
Resolution 0.18°C0.25°C0.23°C0.10°C
Isolation (Input to Output): 2500 Vrms
Accuracy @ 25°C: ± 3°C
Offset Drift: ± 100 ppm/°C
Gain Drift: ± 55 ppm/°C
Operating Temperature Range: 0°C to 60°C
Storage Temperature Range: -25°C to 85°C
RTD Input ModulesPart Number GAIRTD
Input Range: -50°C to 350°C
Resolution: 0.10°C
Accuracy, Across Range @ 25°C: ± 0.8°C
Isolation: 2500 VRMS
Operating Temperature Range: 0°C to 60°C
Storage Temperature Range: -25°C to 85°C