5. Select a group to which you want to add new module by highlighting an
item in the Manager Modules list. Then click the Create New Module
button.
Result: The confirmation window for creating a new module is
displayed.
6. Click the Yes button.
Result: WinPM creates a new module for you.
Deleting Modules
This procedure describes how to use WinPM to delete modules in your 9000
series meter. Do the following to delete an existing module:
1. From the View menu, select Device List.
Result: The Device List window is displayed.
2. On the Device List window, highlight the 9000 series power meter that
you want to configure.
3. Click the right mouse button, and then select Device Configuration from
the drop-down menu that is displayed.
Result: The 9000 Series Meter Configuration window of the selected
meter is displayed.
4. Click the Module Add/Remove button.
Result: The 9000 Series Modules Add/Remove window of the selected
meter is displayed.
5. Select a group that you want to delete an existing module by
highlighting an item in the Manager Modules list box. Then select the
module in the Selected Manager Owns list box.
6. Click the Delete Selected Module button.
Result: The confirmation window is displayed.
7. Click Yes to delete the module.
Result: WinPM deletes the existing module for you. You should wait
until the completion of reloading the linkage to the 9000 series meter
Configuring Existing Modules
This procedure describes how to use WinPM to conf igure the existing
modules by changing the setup registers in your 9000 series meter. Do the
following to configure an existing module:
1. From the View menu, select Device List.
Result: The Device List window is displayed.
238)
You should wait until
reloading the linkage to the
9000 series meter is
complete. If the maximum
number of modules in the
group is exceeded, WinPM
pops up an error message
box.
238)
Before you can delete a
module, you must remove
all links. You cannot delete
a module if any other
modules depend upon the
output of the module.