2-16 9700 POWER METER USER’S GUIDE
Power Quality Monitoring FrameworkThis portion of the factory configuration monitors the phase voltage
signals for sag/swell and transient events, and triggers waveform
recordings when they occur (statistics are also recorded for each event). A
trigger is provided for manual waveform recording, and counters are
included to display the number of events that have occu rred (an additional
trigger provided to reset these counters).
Displayed/Accessible by DefaultDescription of
Parameter or Function WinPM MGT
Module
Name Module
Label Output
Register Label
Sag or Swell Duration lSS1 DistDur
Phase A min Voltage lSS1 DistV1Min
Phase A max Voltage lSS1 DistV1Max
Phase A average Voltage lSS1 DistV1Avg
Phase A Energy variance lSS1 DistV1Engy
Phase B min Voltage lSS1 DistV2Min
Phase B max Voltage lSS1 DistV2Max
Phase B average Voltage lSS1 DistV2Avg
Phase B Energy variance lSS1 DistV2Engy
Phase C min Voltage lSS1 DistV3Min
Phase C max Voltage lSS1 DistV3Max
Phase C average Voltage lSS1 DistV3Avg
Phase C Energy variance lSS1 DistV3Engy
Nominal Voltage at the
beginning of Sag or Swell
disturbance
lSS1
DistNominal
Voltage level considered a Swell lSS1 Swell Lim *
Voltage level considered a Sag l
Sag/Swell #1 Sag/Swell 1
SS1 Sag Lim *
Phase A Transient duration lTR1 TranV1Dur
Phase A Max Peak Transient lTR1 TranV1Max
Phase B Transient duration lTR1 TranV2Dur
Phase B Max Peak Transient lTR1 TranV2Max
Phase C Transient duration lTR1 TranV3Dur
Phase C Max Peak Transient lTR1 TranV3Max
Nominal Voltage at the
beginning of Transient
disturbance
lTR1
TranNominal
Voltage fluctuation amount
considered a Transient
l
Transient #1 Transient 1
TR1 Threshold *
* These are setup registers, not output registers.