Digital Output Modules
Zero Voltage Turn-On, Normally Open, Manual Override Output Modules
AC Outputs DC Outputs
Part Number GDOAC120MO GDOAC240MO GDODC60MO
Nominal Line Voltage: 120 VAC 240 VAC
N/A
Frequency Range: 25 Hz to 70 Hz 25 Hz to 70 Hz
N/A
Maximum Line Voltage:
N/A N/A
60 VDC
Clamping Voltage:
N/A N/A
80 VDC max.
Maximum Off-state
Leakage 2 mA rms @ 60Hz 4 mA rms @ 60Hz 1. 5 mA @ 60 V DC
Load Voltage Range: 24 to 140 VAC 24 to 280 VAC 3 to 60 VDC
Turn-on Time (60 Hz): 8.3 msec max. 8.3 msec max. 20 µsec max.
Turn-off Time (60 Hz): 8.3 msec max. 8.3 msec max. 50 µsec max.
Maximum Surge Current
(peak): 80 Amps @ 60 Hz, 1 cycle; 25
Amps @ 60 Hz, 60 cycles 80 Amps @ 60 Hz, 1 cycle; 25
Amps @ 60 Hz, 60 cycles 5 Amp for 1 second
Load Current Range (rms): 0.03 to 3.5 Amps
On-state Voltage Drop
(peak): 1.5 Volts max.
Power Dissipation: 1.0 Watt/Amp typical
Optical Isolation(Input to
Output): 4000 VAC rms
Operating Temperature
Range: -40°C to +100°C
Storage Temperature
Range: -40°C to +125°C
Standards and Certification: UL File # E58632, CSA File # LR38763
Transient Protection: Meets ANSI 37.90-1989 Surge Withstand Capability Test