2-20 9700 POWER METER USER’S GUIDE
Real T i me Measurements (Core Modules)This portion of the factory configuration contains the real-time phase
voltage and current measurements, harmonics measuremen ts,
symmetrical component data, and output from the device ’s real-time
clock.
Displayed/Accessible by Default
Description of
Parameter or Function WinPM MGT
Module
Name Module
Label Output
Register Label
Phase A L-N Volts ll Vln a *
Phase B L-N Volts ll Vln b
Phase C L-N Volts ll Vln c
Average L-N Volts ll Vln avg
L-L Volts AB ll Vll ab
L-L Volts BC ll Vll bc
L-L Volts CA ll Vll ca
Average L-L Volts ll Vll avg
Phase A Current ll I a
Phase B Current ll I b
Phase C Current ll I c
Average Current ll I avg
Phase A kW ll kW a
Phase B kW ll kW b
Phase C kW ll kW c
kW total ll kW tot
Phase A kVAR ll kVAR a
Phase B kVAR ll kVAR b
Phase C kVAR ll kVAR c
kVAR total ll kVAR tot
Phase A kVA ll kVA a
Phase B kVA ll kVA b
Phase C kVA ll kVA c
kVA total ll kVA tot
PF in Quadrant 1 **
Power Meter Module Power Meter *
Quadrant 1
In addition to the standard Power Meter module, the 9700 Power Meter includes a HS (high-speed) Power Meter and a
MU (meter units) Power Meter modules. Module and output register labels from the HS and MU Power Met er modules
include an HS or MU prefix.
Quadrant Boolean values indicate the quadrant where the Power Factor lies. Only one Quadrant Boolean will be on at
any given time.