3. Operating InformationEnglish
3.8 Closed Loop Control
Closed loop control is only possible when an OPm2 or a serial link is connected to the CombiDrive | ® . |
3.8.1 General Description
The CombiDrive® provides a Proportional/Integral (PI) control function for closed loop control (see Figure 7). PI control is ideal for temperature or pressure control, or other applications where the controlled variable changes slowly or where transient errors are not critical. This control loop is not suitable for use in systems where fast response times are required.
Note: The closed loop function is not designed for speed control, but can be used for this provided that fast response times are not required.
When closed loop PI control is enabled (P201 = 002), all setpoints are calibrated between zero and 100%, i.e. a setpoint of 50.0 = 50%. This allows general purpose control of any process variable that is actuated by motor speed and for which a suitable transducer is available.
Setpoint |
|
|
|
|
|
| |
|
|
|
| Acceleration/ |
|
| |
LowPass |
|
| P | Deceleration |
|
| |
Filter | Scaling | + | Ramp | Motor | |||
| |||||||
|
|
| P202 |
| M | Process | |
|
| – |
|
| e.g. fan | ||
|
|
|
|
| |||
|
|
|
|
|
| ||
P206 | P211, P212 |
| I | P002, P003 | Feedback | ||
|
|
|
| (e.g. duct pressure) | |||
Feedback |
|
| P203, P207 |
|
| Transducer | |
|
|
|
|
| |||
Sample |
|
|
|
|
| ||
|
|
|
|
|
| ||
Rate |
|
|
|
|
| P208 | |
P205 |
|
|
|
|
| ||
|
| Closed Loop Mode Disabled |
|
|
| ||
|
|
|
|
|
| ||
|
|
| P201 = 000 |
|
|
| |
|
|
| Closed Loop Mode Enabled |
|
| Feedback | |
|
|
|
|
| Monitor | ||
|
|
| P201 = 002 | P210 | |||
|
|
|
|
Figure 7: Closed Loop Control
3.8.2 Hardware Setup
Connect the signal wire from the external feedback transducer to control terminal 10. Set jumper JP303 if voltage input type is required (default) or set JP302 if current input type is required.
15 V dc power for the feedback transducer can be supplied from control terminal 8.3.8.3 Parameter Settings
Closed loop control cannot be used unless P201 is first set to 001. Most of the parameters associated with closed loop control are shown in Figure 7. Other parameters which are also associated with closed loop control are as follows:
P001 (value = 007)P061 (value = 012 or 013)P210P220Descriptions of all closed loop control parameters are provided in section 4. For further detailed information about PI operation, refer to the Siemens DA 64 Catalogue.
© STÖBER plc 1997
13 | 05.02.01 |
|