4. Clear Text Display Module & System Parameters | English | ||||||
|
|
|
|
|
|
|
|
Parameter | Function | Range | Description / Notes |
|
|
| |
|
| [Default] |
|
|
|
|
|
P061 | Selection relay output RL1 | 0 - 13 |
|
|
|
|
|
|
| [6] |
|
|
|
|
|
|
|
| Value | Relay function |
| Active 4 |
|
|
|
| 0 | No function assigned (relay not active) |
| Low |
|
|
|
| 1 | Inverter is running |
| High |
|
|
|
| 2 | Inverter frequency 0.0 Hz |
| Low |
|
|
|
| 3 | Motor run right has been selected |
| High |
|
|
|
| 4 | External brake on (see parameters P063/P064) 1 |
| Low |
|
|
|
| 5 | Inverter frequency less than or equal to minimum |
| Low |
|
|
|
|
| frequency |
|
|
|
|
|
| 6 | Fault indication 2 |
| Low |
|
|
|
| 7 | Inverter frequency greater than or equal to setpoint |
| High |
|
|
|
| 8 | Warning active 3 |
| Low |
|
|
|
| 9 | Output current greater than or equal to P065 |
| High |
|
|
|
| 10 | Motor current limit (warning) 3 |
| Low |
|
|
|
| 11 | Motor over temperature (warning) 3 |
| Low |
|
|
|
| 12 | Closed loop motor LOW speed limit |
| High |
|
|
|
| 13 | Closed loop motor HIGH speed limit |
| High |
|
1External brake requires 24 V (max.) dc slave relay.
2Inverter switches off (see parameter P930 and section 5).
3Inverter does not switch off (see parameter P931).
4‘Active low’ = relay OPEN. ‘Active high’ = relay CLOSED.
P062 | 0 - 4 | This enables or disables the | ||||||||
| control | [0] | Operation is the same as for P061 = 4, except that the brake control | |||||||
|
|
| voltage is supplied directly. |
|
|
|
|
| ||
|
|
| 0 = |
| Disabled |
|
|
|
|
|
|
|
| 1 - 3 = Do not use |
|
|
|
|
| ||
|
|
| 4 = |
| Enabled |
|
|
|
|
|
P063 | External brake release delay | 0 - 20.0 | Only effective if the relay output is set to control an external brake (P061 | |||||||
| (seconds) | [1.0] | = 4) or the | |||||||
|
|
| case when the inverter is switched on, it will run at the minimum | |||||||
|
|
| frequency for the time set by this parameter before releasing the brake | |||||||
|
|
| control relay and ramping up (see illustration in P064). | |||||||
P064 | External brake stopping time | 0 - 20.0 | As P063, only effective if the relay output is set to control an external | |||||||
| (seconds) | [1.0] | brake (P061 = 4) or the | |||||||
|
|
| 4). This defines the period for which the inverter continues to run at | |||||||
|
|
| the minimum frequency after ramping down and while the external | |||||||
|
|
| brake is applied. |
|
|
|
|
| ||
|
|
| f |
| ON |
| OFF |
|
| |
|
|
|
|
|
|
| ||||
|
|
| fmin |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| t | |
|
|
|
|
| t |
|
| t |
| A = Brake applied |
|
|
|
|
| P063 | B |
| P064 |
| B = Brake removed |
|
|
| Notes: |
| A |
| A |
| ||
|
|
|
|
|
|
| ||||
|
|
|
| (1) Settings for P063 and P064 should be slightly longer | ||||||
|
|
|
|
| than the actual time taken for the external brake to | |||||
|
|
|
|
| apply and release respectively. |
|
|
(2) Setting P063 or P064 to too high a value, especially
| with P012 set to a high value, can cause an | |
| overcurrent warning or trip as the inverter attempts to | |
| move a locked motor shaft. | |
|
|
|