4. Clear Text Display Module & System Parameters | English |
Parameter | Function | Range |
|
| [Default] |
P910 • | Local/Remote mode | 0 - 4 |
|
| [0] |
Description / Notes
Sets the inverter for local control or remote control over the serial link:
0 = Local control
1 = Remote control (and setting of parameter values)
2 = Local control (but remote control of frequency)
3 = Remote control (but local control of frequency)
4 = Local control (but remote read and write access to parameters and facility to reset trips)
Note: When operating the inverter via remote control (P910 = 1 or 3), the analogue input remains active when P006 = 1 and is added to the setpoint.
P918 •
Specific to
P922 |
| Software version | 0.00 - | Contains the software version number and cannot be changed. | |
|
|
| 99.99 |
|
|
|
|
|
|
| |
P923 | • | Equipment system number | 0 - 255 | You can use this parameter to allocate a unique reference number to | |
|
|
| [0] | the inverter. It has no operational effect. | |
P927 | • |
|
| Specific to | |
P928 | • |
|
| details. (Access only possible with P099 = 1.) | |
P930 |
| Most recent fault code | 0 - 9999 | The last recorded fault code (see section 5) is stored in this | |
|
|
| parameter. It is cleared when the inverter is reset. | ||
P931 |
| Most recent warning type | 0 - 9999 | The last recorded warning is stored in this parameter until power is | |
|
|
| removed from the inverter: | ||
|
|
|
| 002 = | Current limit active |
|
|
|
| 003 = | Voltage limit active |
|
|
|
| 005 = | Inverter over temperature (internal PTC) |
P944 |
| Reset to factory default settings | 0 - 1 | Set to ‘1’ and then press P to reset all parameters except P101 to the | |
|
|
| [0] | factory default settings. | |
P947 |
|
|
|
|
|
P958 |
|
|
|
|
|
P963 |
|
|
| Specific to | |
P967 |
|
|
| details. (Cannot be accessed unless P099 = 1.) | |
|
|
|
|
| |
P968 |
|
|
|
|
|
P970 |
|
|
|
|
|
P971 | • | EEPROM storage control | 0 - 1 | 0 = Changes to parameter settings (including P971) are lost when | |
|
|
| [1] | power is removed. |
1 = Changes to parameter settings are retained during periods when power is removed.
IMPORTANTTake care not to exceed the EEPROM write cycle limit of 50,000/parameter (approx.) when using the serial link to update parameters, otherwise data loss or corruption may occur. Read cycles are unlimited.