4. Clear Text Display Module & System Parameters

 

 

 

 

 

English

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter

Function

Range

Description / Notes

 

 

 

 

 

 

 

 

 

 

 

[Default]

 

 

 

 

 

 

 

 

 

 

P027

Skip frequency 2 (Hz)

0 - 120.00

See P014.

 

 

 

 

 

 

 

 

 

 

 

[0.00]

 

 

 

 

 

 

 

 

 

 

P028

Skip frequency 3 (Hz)

0 - 120.00

See P014.

 

 

 

 

 

 

 

 

 

 

 

[0.00]

 

 

 

 

 

 

 

 

 

 

P029

Skip frequency 4 (Hz)

0 - 120.00

See P014.

 

 

 

 

 

 

 

 

 

 

 

[0.00]

 

 

 

 

 

 

 

 

 

 

P031

Jog frequency right (Hz)

0 - 120.00

Jogging is used to advance the motor by small amounts. It is

 

 

 

[5.00]

controlled via the JOG button or with a non-latching switch on one of

 

 

 

 

the digital inputs (P051 to P053).

 

 

 

 

 

 

 

 

 

 

 

If jog right is enabled (DINn = 7), this parameter controls the frequency at

 

 

 

 

which the inverter will run when the switch is closed. Unlike other setpoints, it

 

 

 

 

can be set lower than the minimum frequency.

 

 

 

 

 

 

P032

Jog frequency left (Hz)

0 - 120.00

If jog left is enabled (DINn = 8), this parameter controls the frequency at which

 

 

 

[5.00]

the inverter will run when the switch is closed. Unlike other setpoints, it can be

 

 

 

 

set lower than the minimum frequency.

 

 

 

 

 

 

 

P035

 

Reverse motor direction

0 - 1

0 = Normal direction control.

 

 

 

 

 

 

 

 

 

 

[0]

1 = Direction control is reversed.

 

 

 

 

 

 

 

P041

Fixed frequency 1 (Hz)

0 - 120.00

Valid if P006 = 2 and P053 = 6 or 18 or P051 = P052 = P053 = 17.

 

 

 

[5.00]

 

 

 

 

 

 

 

 

 

 

P042

Fixed frequency 2 (Hz)

0 - 120.00

Valid if P006 = 2 and P052 = 6 or 18 or P051 = P052 = P053 = 17.

 

 

 

[10.00]

 

 

 

 

 

 

 

 

 

 

P043

Fixed frequency 3 (Hz)

0 - 120.00

Valid if P006 = 2 and P051 = 6 or 18 or P051 = P052 = P053 = 17.

 

 

 

[15.00]

 

 

 

 

 

 

 

 

 

 

P044

Fixed frequency 4 (Hz)

0 - 120.00

Valid if P006 = 2 and P051 = P052 = P053 = 17.

 

 

 

 

 

 

 

 

[20.00]

 

 

 

 

 

 

 

 

 

 

P045

 

Inversion fixed setpoints for

0 - 7

Sets the direction of rotation for the fixed frequency:

 

 

 

 

 

fixed frequencies 1 - 4

[0]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FF 1

FF 2

 

FF 3

 

FF 4

 

 

 

 

 

 

P045 = 0

 

 

 

 

 

 

 

 

P045 = 1

 

 

 

 

 

 

 

 

P045 = 2

 

 

 

 

 

 

 

 

P045 = 3

 

 

 

 

 

 

 

 

P045 = 4

 

 

 

 

 

 

 

 

P045 = 5

 

 

 

 

 

 

 

 

P045 = 6

 

 

 

 

 

 

 

 

P045 = 7

 

 

 

 

 

 

 

 

Fixed setpoints not inverted.

 

 

 

 

 

 

 

Fixed setpoints inverted.

 

 

 

P046

Fixed frequency 5 (Hz)

0 - 120.00 Valid if P006 = 2 and P051 = P052 = P053 = 17.

 

 

[25.00]

 

 

 

 

 

 

 

 

P047

Fixed frequency 6 (Hz)

0 - 120.00 Valid if P006 = 2 and P051 = P052 = P053 = 17.

 

 

[30.00]

 

 

 

 

 

 

 

 

P048

Fixed frequency 7 (Hz)

0 - 120.00 Valid if P006 = 2 and P051 = P052 = P053 = 17.

 

 

[35.00]

 

 

 

 

 

 

 

 

P050

Inversion fixed setpoints for

0 - 7

Sets the direction of rotation for the fixed frequency:

 

fixed frequencies 5 - 7

[0]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FF 5

FF 6

 

FF 7

 

 

 

 

 

P050 = 0

 

 

 

 

 

 

P050 = 1

 

 

 

 

 

 

P050 = 2

 

 

 

 

 

 

P050 = 3

 

 

 

 

 

 

P050 = 4

 

 

 

 

 

 

P050 = 5

 

 

 

 

 

 

P050 = 6 or 7

 

 

 

 

 

 

Fixed setpoints not inverted.

 

 

 

 

 

 

 

Fixed setpoints inverted.

 

 

 