English

 

4.

Clear Text Display Module & System Parameters

 

 

 

 

 

 

 

 

Parameter

Function

Range

Description / Notes

 

 

 

 

 

[Default]

 

 

 

 

 

 

P018

Automatic restart after fault

0 - 1

Automatic restart after fault:

 

 

 

 

 

[0]

0 =

Disabled

 

 

 

 

 

 

1 = The inverter will attempt to restart up to 5 times after a fault.

 

 

 

 

If the fault is not cleared after the 5th attempt, the inverter

 

 

 

 

will remain in the fault state until reset.

 

 

 

 

There is an increasing time delay between each restart

 

 

 

 

attempt.

 

 

 

P019

Skip frequency bandwidth (Hz)

0 - 10.00

Frequencies set by P014, P027, P028 or P029 that are within +/- the

 

 

[2.00]

value of P019 are suppressed.

 

P020

Flying start ramp time (seconds)

0.50 - 25.0

Used in conjunction with P016 (set longer times if persistent F002

 

 

[5.0]

trips occur).

 

 

 

 

P021

Minimum analogue frequency

0 - 120.00

Frequency corresponding to the lowest analogue input value, i.e.

 

(Hz)

[0.00]

0 V / 0 mA or 2 V / 4 mA. This can be set to a higher value than P022

 

 

 

to give an inverse relationship between analogue input and frequency

 

 

 

output (see diagram in P022).

 

P022

Maximum analogue frequency

0 - 120.00

Frequency corresponding to the highest analogue input value, i.e.

 

(Hz)

[50.00]

10 V / 20 mA, determined by P023. This can be set to a lower value

 

 

 

than P021 to give an inverse relationship between analogue input and

 

 

 

frequency output.

 

 

 

 

 

 

i.e.

f

P021

 

 

 

 

 

 

 

 

P022

 

 

 

 

 

 

 

 

 

 

 

 

P022

 

 

 

 

 

P021

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note:

 

 

V / I

 

 

 

The output frequency is limited by values entered for

 

 

 

 

P012/P013.

 

 

 

P023

Analogue input type

0 - 2

Selects analogue input type according to the setting of jumpers

 

 

[2]

JP300/JP301:

 

 

 

 

 

 

 

JP301 closed

OR

JP300 closed

 

 

 

0 = 0 V to 10 V

0 mA to 20 mA

 

 

 

1 = 2 V to 10 V

4 mA to 20 mA

 

 

 

2 = [2 V* to 10 V]

4 mA* to 20 mA

 

 

 

* The inverter will come to a controlled stop if V < 1 V or 2 mA.

 

 

 

WARNING: The motor can automatically run without a

 

 

 

 

 

potentiometer or voltage source connected

 

 

 

 

 

between pins 3 and 4.

 

 

 

 

 

With P023=2, the motor will automatically start

 

 

 

 

 

when V exceeds 2 V. This equally applies to

 

 

 

 

 

analogue and digital control (i.e. P006 = 0 or 1).

 

P024

Analogue setpoint addition

0 - 2

If the inverter is not in analogue mode (P006 = 0 or 2), setting this

 

 

[0]

parameter to ‘1’ causes the analogue input value to be added.

 

 

 

0 =

No addition.

 

 

 

 

 

 

1 = Addition of the analogue setpoint (defined by P023) to the

 

 

 

 

fixed frequency or the motor potentiometer frequency.

 

 

 

2 = Scaling of digital/fixed setpoint by analogue input (P023) in

 

 

 

Note:

the range 0 - 100%.

 

 

 

By selecting a combination of reversed negative fixed

 

 

 

 

frequency settings and analogue setpoint addition, it is

 

possible to configure the inverter for ‘centre zero’ operation

 

with a +/-5 V supply or a 0 - 10 V potentiometer so that the

 

output frequency can be 0 Hz at any position, including the

 

centre position.

 

 

 

 

© STÖBER plc 1998

05.02.01

18