English | 4. | Clear Text Display Module & System Parameters | ||
|
|
|
| |
Parameter | Function | Range | Description / Notes |
|
|
| [Default] |
|
|
P051
P052
P053
Selection control function, DIN1 | 0 - 19 |
(terminal 5), fixed frequency 3 | [1] |
or binary fixed frequency bit 0. |
|
Selection control function, DIN2 | 0 - 19 |
(terminal 6), fixed frequency 2. | [2] |
or binary fixed frequency bit 1. |
|
Selection control function, DIN3 | 0 - 19 |
(terminal 7), fixed frequency 1 | [10] |
or binary fixed frequency bit 2. |
|
Value | Function of P051 to P053 | Function, | Function, |
|
| low state | high state |
0 | Input disabled | - | - |
1 | ON right | Off | On right |
2 | ON left | Off | On left |
3 | Reverse | Normal | Reverse |
4 | OFF2 * | OFF2 | On |
5 | OFF3 * | OFF3 | On |
6 | Fixed frequencies 1 - 3 | Off | On |
7 | Jog right | Off | Jog right |
8 | Jog left | Off | Jog left |
9 | Remote operation | Local | Remote |
10 | Fault code reset | Off | Reset on |
11 |
|
| rising edge |
Increase frequency ** | Off | Increase | |
12 | Decrease frequency ** | Off | Decrease |
13 | Disable analogue input | Analogue | Analogue |
14 | (setpoint is 0.0 Hz) | on | disabled |
Disable the ability to change | ‘P’ Enabled | ‘P’ Disabled | |
15 | parameters | Off | Brake on |
Enable dc brake | |||
16 | Do not use | - | - |
17 | Binary fixed frequency control | Off | On |
18 | (fixed frequencies 1 - 7) | Off | On |
As 6, but input high will also | |||
19 | request RUN * | Yes (F012) | No |
External trip/PTC |
*See section 3.7.
**Only effective when P007 = 0.
Binary Coded Fixed Frequency Mapping | ||||
| (P051, P052, P053 = 17) |
| ||
|
| DIN3 (P053) | DIN2 (P052) | DIN1 (P051) |
STOP |
| 0 | 0 | 0 |
RUN to FF1 (P041) |
| 0 | 0 | 1 |
RUN to FF2 (P042) |
| 0 | 1 | 0 |
RUN to FF3 (P043) |
| 0 | 1 | 1 |
RUN to FF4 (P044) |
| 1 | 0 | 0 |
RUN to FF5 (P046) |
| 1 | 0 | 1 |
RUN to FF6 (P047) |
| 1 | 1 | 0 |
RUN to FF7 (P048) |
| 1 | 1 | 1 |
P056 |
| Digital input debounce time | 0 - 2 | Use a fast response time only when a ‘clean’ input signal | |
|
|
| [0] | is used, e.g. from a PLC. Use a slow response time to | |
|
|
|
| allow filtering of the signal if a noisy input (e.g. a switch) is | |
|
|
|
| used. |
|
|
|
|
| 0 | = 12.5 ms |
|
|
|
| 1 | = 7.5 ms |
|
|
|
| 2 | = 2.5 ms |
|
|
|
|
| |
P058 | ● | RUN command delay (seconds) | 0.0 - 650.0 | Sets a time delay before the RUN command takes effect. | |
|
|
| [0.0] | This parameter affects run commands from all sources |
except the RUN button on the OPm2 (this activates the drive immediately)..