Clear Text Display Module & System Parameters

 

 

 

 

Parameter

Function

Range

Description / Notes

 

 

 

[Default]

 

 

P051

P052

P053

Selection control function, DIN1

0 - 19

(terminal 5), fixed frequency 3

[1]

or binary fixed frequency bit 0.

 

Selection control function, DIN2

0 - 19

(terminal 6), fixed frequency 2.

[2]

or binary fixed frequency bit 1.

 

Selection control function, DIN3

0 - 19

(terminal 7), fixed frequency 1

[10]

or binary fixed frequency bit 2.

 

ValueFunction of P051 to P053

Function,

Function,

 

 

low state

high state

0

Input disabled

-

-

1

ON right

Off

On right

2

ON left

Off

On left

3

Reverse

Normal

Reverse

4

OFF2 *

OFF2

On

5

OFF3 *

OFF3

On

6

Fixed frequencies 1 - 3

Off

On

7

Jog right

Off

Jog right

8

Jog left

Off

Jog left

9

Remote operation

Local

Remote

10

Fault code reset

Off

Reset on

11

 

 

rising edge

Increase frequency **

Off

Increase

12

Decrease frequency **

Off

Decrease

13

Disable analogue input

Analogue

Analogue

14

(setpoint is 0.0 Hz)

on

disabled

Disable the ability to change

‘P’ Enabled

‘P’ Disabled

15

parameters

Off

Brake on

Enable dc brake

16

Do not use

-

-

17

Binary fixed frequency control

Off

On

18

(fixed frequencies 1 - 7)

Off

On

As 6, but input high will also

19

request RUN *

Yes (F012)

No

External trip/PTC

*See section 3.7.

**Only effective when P007 = 0.

Binary Coded Fixed Frequency Mapping

 

(P051, P052, P053 = 17)

 

 

 

DIN3 (P053)

DIN2 (P052)

DIN1 (P051)

STOP

 

0

0

0

RUN to FF1 (P041)

 

0

0

1

RUN to FF2 (P042)

 

0

1

0

RUN to FF3 (P043)

 

0

1

1

RUN to FF4 (P044)

 

1

0

0

RUN to FF5 (P046)

 

1

0

1

RUN to FF6 (P047)

 

1

1

0

RUN to FF7 (P048)

 

1

1

1

P056

 

Digital input debounce time

0 - 2

Use a fast response time only when a ‘clean’ input signal

 

 

 

[0]

is used, e.g. from a PLC. Use a slow response time to

 

 

 

 

allow filtering of the signal if a noisy input (e.g. a switch) is

 

 

 

 

used.

 

 

 

 

 

0

= 12.5 ms

 

 

 

 

1

= 7.5 ms

 

 

 

 

2

= 2.5 ms

 

 

 

 

 

P058

RUN command delay (seconds)

0.0 - 650.0

Sets a time delay before the RUN command takes effect.

 

 

 

[0.0]

This parameter affects run commands from all sources

except the RUN button on the OPm2 (this activates the drive immediately)..