English | 2. Installation |
2.3 Electrical Installation
Remove the four M5
Notes: (1) Refer to the electrical data table for cable sizes (see section 6).
(2)We recommend introducing a `drip loop' when connecting the mains and control cables(see Figure 5).
CAUTION
The printed circuit boards contain CMOS components that are particularly sensitive to static electricity. For this reason, avoid touching the boards or components with your hands or metal objects.
Mains Connector * |
| LED | LED |
|
L1 L2 L3 |
| (Green) | (Yellow) |
|
|
|
|
| |
Control Cable Connector |
|
|
| |
| (PL800) |
|
|
|
12 | 1 |
| - | + |
| 1 | 4 |
|
|
| OPm2 Connector | Control |
| |
|
| (SK200) | Potentiometer | |
|
|
| (R314) |
|
| Jumpers for |
| Jumpers for |
| PI Input Type | Analogue Input Type | |
| Default = V |
| Default = V |
V | JP303 | V | JP301 |
I | JP302 | I | JP300 |
Note: Jumper in ‘V’ position = voltage input (default) Jumper in ‘I’ position = current input
IMPORTANT
Ensure that the following tightening torques are used:
Electrical terminal screws: | 1.1 Nm |
Access cover retaining screws: | 4.0 Nm |
Gland hole covers: | 1.0 Nm |
*Check that the supply voltage is correct for the COMBIMASTERused by referring to the voltage code part of the order number (see section 6).
Figure 1: Electrical Connection Diagram
© STÖBER plc 1998
05.02.01 | 6 |
|