4. Clear Text Display Module & System Parameters

English

 

 

 

 

 

Parameter

Function

Range

Description / Notes

 

 

 

 

[Default]

 

 

 

P078

Continuous boost (%)

0 - 250

Operates continuously over the whole frequency range.

 

 

 

[100]

For many applications it is necessary to increase low frequency

 

 

 

 

torque. This parameter sets the start-up voltage at 0 Hz to adjust the

 

 

 

 

available torque for low frequency operation. 100% setting will

 

 

 

 

produce rated motor current at low frequencies.

 

 

 

 

WARNING:

If P078 is set too high, overheating of the motor

 

 

 

 

 

and/or an overcurrent trip (F002) can occur.

 

P079

Starting boost (%)

0 - 250

For drives which require a high initial starting torque, it is possible to

 

 

 

[0]

set an additional current (added to the setting in P078) during

 

 

 

 

ramping. This is only effective during initial start up and until the

 

 

 

 

frequency setpoint is reached.

 

 

 

 

Note: This increase is in addition to P078, but the total is limited to

 

 

 

 

250%.

 

 

P081

 

Nominal frequency for motor

0 - 120.00

 

 

 

 

 

(Hz)

[œœœ]

 

 

 

P082

 

Nominal speed for motor (RPM)

0 - 9999

 

 

 

 

 

 

[œœœ]

 

 

 

P083

 

Nominal current for motor (A)

0.1 - 99.9

‘These parameters are set in the factory and should not be changed

 

 

 

[œœœ]

under normal circumstances.

P084

 

Nominal voltage for motor (V)

0 - 1000

 

 

 

 

 

 

[œœœ]

 

 

 

P085

 

Nominal power for motor

0 - 100.0

 

 

 

 

 

(kW/hp)

[œœœ]

 

 

 

P086

Motor current limit (%)

0 - 250

The motor current can be limited with this parameter. If the set value

 

is exceeded, the output frequency is reduced until the current falls

 

 

 

[150]

 

 

 

 

below this limit. During this process, both LEDs will flash (see section

 

 

 

 

3.6).

 

 

P087

Motor PTC enable

0 - 1

 

 

[0]

Change this parameter only when the PTC option is fitted.

0 = Disabled

1 = Motor PTC enabled

Note: If P087 = 1 and the PTC input goes high then the inverter will trip (fault code F004). Note that if the internal PTC gets too hot, the inverter will trip (fault code F005).

P089

Stator resistance (

)

0.01-

Set in the factory. Do not adjust!

 

 

 

 

100.00

 

 

 

 

 

 

[œœœ]

 

 

P091

Serial link slave address

0 - 30

Up to 31 CombiDrive ® can be connected via the serial link and

 

 

 

 

[0]

controlled by a computer or PLC using the USS protocol. This

 

 

 

 

 

parameter sets a unique address for the inverter.

P092

Serial link baud rate

 

3 - 7

Sets the baud rate of the RS485 serial interface (USS protocol):

 

 

 

 

[6]

3 =

1200 baud

 

 

 

 

 

4 =

2400 baud

 

 

 

 

 

5 =

4800 baud

 

 

 

 

 

6 =

9600 baud

 

 

 

 

 

7 =

19200 baud

 

 

 

 

 

Note:

Some RS232 to RS485 converters are not capable of

 

 

 

 

 

 

baud rates higher than 4800.