English7. Supplementary Information
7. SUPPLEMENTARY INFORMATION
7.1 Application Example
Setup procedure for a simple application
Application requirements: | Normal operating frequency set within range 15 - 50 Hz via potentiometer. |
| |
CombiDrive used: | Any model. |
® |
|
Procedure: | (1) Remove the link (if fitted) between control terminals 5 and 8. |
(2)Connect a simple on/off switch to control terminals 6 and 8 for reverse rotation.
(3)Connect a 4.7 kΩ ποτεντιο∝ετερ το τηε χοντρολ τερ∝ιναλσ(see Figure 4).
(4)Set jumper JP301 (‘V’ - voltage) - see Figure 3.
(5)Set the internal and external potentiometers fully
(6)Turn the internal potentiometer clockwise until the motor rotates at a speed that approximates to 15 Hz.
(7)The external potentiometer now has a range of between 15 Hz at its lowest setting and 50 Hz at its highest setting.
7.2USS Status Codes
The following list gives the meaning of status codes displayed on the OPm2 when the serial link is in use and parameter P001 is set to 006:
001 Message OK
002Slave address received
100Invalid start character
101Timeout
102Checksum error
103Incorrect message length
104Parity fail
Notes
(1)The display flashes whenever a byte is received, thus giving a basic indication that a serial link connection is established.
(2)If ‘100’ flashes on the display continuously, this usually indicates a bus termination fault.
© STÖBER plc 1998