4. Clear Text Display Module & System Parameters | English | ||||||
|
|
|
|
| |||
Parameter | Function | Range | Description / Notes |
| |||
|
| [Default] |
|
|
|
|
|
P123 | Enable/disable JOG button | 0 - 1 | 0 = JOG button disabled. | ||||
|
| [1] | 1 = JOG button enabled (only possible if P007 = 1). |
| |||
P124 | Enable/disable ∆ and ∇ buttons | 0 - 1 | 0 = | ∆ | and ∇ | buttons disabled. | |
|
| [1] | 1 = | ∆ | and ∇ buttons enabled (only possible if P007 = 1). | ||
|
|
| Note: | This applies for frequency adjustment only. The buttons can | |||
|
|
|
|
| still be used to change parameter values. |
| |
P125 | Reverse direction inhibit | 0 - 1 | 0 = | Reverse direction disabled. Inhibits reverse commands from | |||
|
| [1] |
| ALL sources (reverse RUN commands result in forward rotation) |
1 = Normal operation (FORWARD/REVERSE operation allowed)
P131 | Frequency setpoint (Hz) | 0.00 |
|
| |
P132 | Motor current (A) | 0.0 - 99.9 |
|
| |
P134 | DC link voltage (V) | 0 - 1000 |
|
| |
P135 | Motor RPM | 0 - 40000 |
|
| |
P137 | Output voltage (V) | 0 - 1000 |
|
|
P140 |
| Most recent fault code | 0 - 9999 | The last recorded fault code (see section 5) is stored in this | ||
|
|
| parameter. It is cleared when the inverter is reset. | |||
|
|
|
| This is a copy of the code stored in P930. | ||
|
|
|
|
| ||
P141 |
| Most recent fault code | 0 - 9999 | This parameter stores the last recorded fault code prior to that stored | ||
|
|
| in P140/P930. |
| ||
P142 |
| Most recent fault code | 0 - 9999 | This parameter stores the last recorded fault code prior to that stored | ||
|
|
| in P141. |
| ||
P143 |
| Most recent fault code | 0 - 9999 | This parameter stores the last recorded fault code prior to that stored | ||
|
|
| in P142. |
| ||
P151 | • | Green LED function | 0 - 5 | 0 | = Off |
|
|
|
| [4] | 1 | = On |
|
|
|
|
| 2 | = Fault mode: | On = Tripped |
|
|
|
| 3 |
| Flashing = Warning |
|
|
|
| = Running mode:On = Motor running | ||
|
|
|
| stationary | Flashing = Inverter on but motor | |
|
|
|
|
| ||
|
|
|
| 4 | = Default mode (see table in section 3.6) | |
|
|
|
| 5 | = Not used |
|
P152 | • | Yellow LED function | 0 - 5 | 0 | = Off |
|
|
|
| [5] | 1 | = On |
|
|
|
|
| 2 | = Fault mode: | On = Tripped |
|
|
|
| 3 |
| Flashing = Warning |
|
|
|
| = Running mode:On = Motor running | ||
|
|
|
| stationary | Flashing = Inverter on but motor | |
|
|
|
|
| ||
|
|
|
| 4 | = Not used |
|
|
|
|
| 5 | = Default mode (see table in section 3.6) | |
P201 |
| PI closed loop mode | 0 - 2 | 0 = Normal operation (closed loop control disabled). | ||
|
|
| [0] | 1 = Not used |
| |
|
|
|
| 2 = Closed loop control using PI input for transducer feedback. | ||
P202 | • | P gain (%) | 0.0 - 999.9 | Proportional gain. |
| |
|
|
| [1.0] |
|
|
|