5. FAULT CODES
Fault codes are only available when an OPm2 is connected to the CombiDrive® .In the event of a failure, the CombiDrive® switches off and a fault code appears on the LCD screen. The last fault that occurred is stored in parameter P930. e.g. ‘0003' indicates that the last error was F003.
Fault Code | Cause | Corrective Action |
F001 | Overvoltage | Check whether supply voltage is within the limits indicated on the rating plate. |
|
| Increase the ramp down time (P003). |
|
| Check whether the required braking power is within the specified limits. |
F002 | Overcurrent | Check motor lead and motor for |
|
| Increase the |
|
| Reduce the boost set in P078 and P079. |
|
| Check whether the motor is obstructed or overloaded. |
F003 | Overload | Check whether the motor is overloaded. |
F004 | Overheating of motor | Check if motor is overloaded. |
| (monitoring with PTC) | Check the connections to the PTC. |
|
| Has P087 been set to 1 without a PTC being connected? |
F005 | Inverter overtemperature | Check that the ambient temperature is not too high. |
| (internal PTC) | The motor speed may be too low for a given load. |
F006 | Power module overtemperature | Check that the ambient temperature is not too high. |
F008 | USS protocol timeout | Check the serial interface. |
|
| Check the settings of the bus master and P091 - P093. |
|
| Check whether the timeout interval is too short (P093). |
F009 | Undervoltage | Check that the power supply is supplying enough voltage to the inverter. |
F010 | Initialisation fault / Parameter loss * | Check the entire parameter set. Set P009 to `0000' before power down. |
F011 | Internal interface fault * | Switch off power and switch on again. |
F012 | External trip | Source of trip is digital input (configured as an external trip input) going low - |
|
| check the external source. |
F013 | Programme fault * | Switch off power and switch on again. |
F018 | Auto restart after fault | Automatic restart after fault (P018) is pending. |
|
| WARNING: The motor shaft may start to rotate at any time. |
F030 | PROFIBUS link failure | Check the integrity of the link. |
F031 | Option module link failure | Check the integrity of the link. |
F033 | PROFIBUS configuration error | Check the PROFIBUS configuration. |
F036 | PROFIBUS module watchdog trip | Replace PROFIBUS module |
F074 | Motor overtemperature by I2t | Check that the motor current does not exceed the value set in P083. |
| calculation |
|
F106 | Parameter fault P006 | Parameterise fixed frequency(ies) and/or motor potentiometer on the digital |
|
| inputs. |
F112 | Parameter fault P012/P013 | Set parameter P012 < P013. |
F151 - F153 | Digital input parameter fault | Check the settings of digital inputs P051 to P053. |
F201 | P006 = 1 while P201 = 2 | Change parameter P006 and/or P201. |
F212 | Parameter fault P211/P212 | Set parameter P211 < P212. |
* Ensure that the wiring guidelines described in section 2.1 have been complied with.
When the fault has been corrected, restart the inverter and the motor will run if the fault has been cleared.