Clear Text Display Module & System Parameters

 

 

 

 

 

Parameter

Function

Range

Description / Notes

 

 

 

[Default]

 

 

 

P093

Serial link timeout (seconds)

0 - 240

This is the maximum permissible period between two incoming data

 

 

[0]

telegrams. This feature is used to turn off the inverter in the event of a

 

 

 

communications failure.

 

 

 

Timing starts after a valid data telegram has been received and if a

 

 

 

further data telegram is not received within the specified time period,

 

 

 

the inverter will trip and display fault code F008.

 

 

 

Setting the value to zero switches off the control.

 

P094

Serial link nominal system

0 - 120.00

Setpoints are transmitted to the inverter via the serial link as

 

setpoint (Hz)

[50.00]

percentages. The value entered in this parameter represents 100%

 

 

 

(HSW = 4000H).

 

P095

USS compatibility

0 - 2

0 = Compatible with 0.1 Hz resolution

 

 

[0]

1 = Enable 0.01 Hz resolution

 

 

 

2 = HSW is not scaled but represents the actual frequency value to

 

 

 

a resolution of 0.01 Hz (e.g. 5000 = 50 Hz).

 

P099

Communication adapter type

0 - 1

0 = Option module not present

 

 

[0]

1 = PROFIBUS module (enables parameters relating to PROFIBUS)

 

P101

Operation for Europe or USA

0 - 1

This sets the inverter for European or USA supply and motor

 

 

[0]

frequency:

 

 

 

0 = Europe (50 Hz)

 

 

 

1 = USA (60 Hz)

 

 

 

Note:

After setting P101 = 1 the CombiDrive ® must be reset to

 

 

 

 

factory defaults. i.e. P944 = 1 to automatically set P013 =

 

 

 

 

60 Hz, P022 = 60 Hz, P081 = 60 Hz, P082 = 1680 rpm and

 

 

 

 

P085 will be displayed in hp.

 

P111

Inverter power rating (kW/hp)

0.0 - 10.00

Read-only parameter that indicates the power rating of the inverter in

 

 

[œœœ]

kW. e.g. 0.55 = 550 W

 

 

 

Note:

If P101 = 1 then the rating is displayed in hp.

P112

Inverter type

1 - 8

 

 

[8]

Read-only parameter.

1 = MICROMASTER series 2 (MM2)

2 =

CombiDrive

®

 

 

3 =

MIDIMASTER

 

4 = MICROMASTER Junior (MMJ)

5 = MICROMASTER series 3 (MM3)

6 = MICROMASTER Vector (MMV)

7 =

MIDIMASTER Vector (MDV)

8 =

CombiDrive ® series 2

P113

COMBIMASTER model

24 - 29

Read-only parameter.

 

 

[-]

24 = CM150/3

 

 

 

25 = CM220/3

 

 

 

26 = CM300/3

 

 

 

27 = CM400/3

 

 

 

28 = CM550/3

 

 

 

29 = CM750/3

P121

Enable/disable RUN button

0 - 1

0 = RUN button disabled.

 

 

[1]

1 = RUN button enabled (only possible if P007 = 1).

P122

Enable/disable

0 - 1

0 = FORWARD/REVERSE button disabled.

 

FORWARD/REVERSE button

[1]

1 = FORWARD/REVERSE button enabled (only possible if P007 = 1).