English |
| 4. | Clear Text Display Module & System Parameters | ||
|
|
|
|
| |
Parameter | Function | Range | Description / Notes |
| |
|
| [Default] |
|
|
|
P093 • | Serial link timeout (seconds) | 0 - 240 | This is the maximum permissible period between two incoming data | ||
|
| [0] | telegrams. This feature is used to turn off the inverter in the event of a | ||
|
|
| communications failure. | ||
|
|
| Timing starts after a valid data telegram has been received and if a | ||
|
|
| further data telegram is not received within the specified time period, | ||
|
|
| the inverter will trip and display fault code F008. | ||
|
|
| Setting the value to zero switches off the control. |
| |
P094 • | Serial link nominal system | 0 - 120.00 | Setpoints are transmitted to the inverter via the serial link as | ||
| setpoint (Hz) | [50.00] | percentages. The value entered in this parameter represents 100% | ||
|
|
| (HSW = 4000H). |
| |
P095 • | USS compatibility | 0 - 2 | 0 = Compatible with 0.1 Hz resolution | ||
|
| [0] | 1 = Enable 0.01 Hz resolution | ||
|
|
| 2 = HSW is not scaled but represents the actual frequency value to | ||
|
|
| a resolution of 0.01 Hz (e.g. 5000 = 50 Hz). |
| |
P099 • | Communication adapter type | 0 - 1 | 0 = Option module not present | ||
|
| [0] | 1 = PROFIBUS module (enables parameters relating to PROFIBUS) |
| |
P101 • | Operation for Europe or USA | 0 - 1 | This sets the inverter for European or USA supply and motor | ||
|
| [0] | frequency: | ||
|
|
| 0 = Europe (50 Hz) | ||
|
|
| 1 = USA (60 Hz) | ||
|
|
| Note: | After setting P101 = 1 the CombiDrive ® must be reset to | |
|
|
|
| factory defaults. i.e. P944 = 1 to automatically set P013 = | |
|
|
|
| 60 Hz, P022 = 60 Hz, P081 = 60 Hz, P082 = 1680 rpm and | |
|
|
|
| P085 will be displayed in hp. |
|
P111 | Inverter power rating (kW/hp) | 0.0 - 10.00 | |||
|
| [] | kW. e.g. 0.55 = 550 W | ||
|
|
| Note: | If P101 = 1 then the rating is displayed in hp. |
P112 | Inverter type | 1 - 8 |
|
| [8] |
1 = MICROMASTER series 2 (MM2)
2 = | CombiDrive | ® |
|
| |
3 = | MIDIMASTER |
|
4 = MICROMASTER Junior (MMJ) |
5 = MICROMASTER series 3 (MM3)
6 = MICROMASTER Vector (MMV)
7 = | MIDIMASTER Vector (MDV) |
8 = | CombiDrive ® series 2 |
P113 | COMBIMASTER model | 24 - 29 | |
|
| 24 = CM150/3 | |
|
|
| 25 = CM220/3 |
|
|
| 26 = CM300/3 |
|
|
| 27 = CM400/3 |
|
|
| 28 = CM550/3 |
|
|
| 29 = CM750/3 |
P121 | Enable/disable RUN button | 0 - 1 | 0 = RUN button disabled. |
|
| [1] | 1 = RUN button enabled (only possible if P007 = 1). |
P122 | Enable/disable | 0 - 1 | 0 = FORWARD/REVERSE button disabled. |
| FORWARD/REVERSE button | [1] | 1 = FORWARD/REVERSE button enabled (only possible if P007 = 1). |
© STÖBER plc 1998
05.02.01 | 24 |
|