| 4. | Clear Text Display Module & System Parameters | ||||||||
|
|
|
|
|
|
|
|
|
| ||
Parameter | Function | Range | Description / Notes |
|
|
|
| ||||
|
| [Default] |
|
|
|
|
|
|
|
|
|
P065 | Current threshold for relay (A) | 0 - 99.9 | This parameter is used when P061 = 9. The relay switches on when | ||||||||
|
| [1.0] | the motor current is greater than the value of P065 and switches off | ||||||||
|
|
| when the current falls to 90% of the value of P065 (hysteresis). |
| |||||||
P071 • | Slip compensation (%) | 0 - 200 | The inverter can estimate the amount of slip in an | ||||||||
|
| [0] | asynchronous motor at varying loads and increase its | ||||||||
|
|
| output frequency to compensate. This parameter `fine | ||||||||
|
|
| tunes' the compensation for different motors in the range | ||||||||
|
|
| 0 - 200% of the inverter's nominal estimate. |
|
|
|
| ||||
P072 • | Slip limit (%) | 0 - 500 | This limits the slip of the motor to prevent | ||||||||
|
| [250] | (stalling), which can occur if slip is allowed to increase | ||||||||
|
|
| indefinitely. When the slip limit is reached, the inverter | ||||||||
|
|
| reduces the frequency until the level of slip is acceptable. |
| |||||||
P073 • | DC injection braking (%) | 0 - 250 | This stops the motor by applying a DC current. This causes heat to be | ||||||||
|
| [0] | generated in the motor rather than the inverter and holds the shaft | ||||||||
|
|
| stationary until the end of the braking period. Braking is effective for | ||||||||
|
|
| the period of time set by P003. |
|
|
|
| ||||
|
|
| The DC brake can be activated using DIN1 - DIN3 (braking is active | ||||||||
|
|
| for as long as the DIN is high - see P051 - P053). |
|
|
|
| ||||
|
|
| WARNING: | Frequent use of long periods of dc injection | |||||||
|
|
|
|
| braking can cause the motor to overheat. | ||||||
|
|
|
|
| If DC injection braking is enabled via a digital | ||||||
|
|
|
|
| input then DC current is applied for as long as the | ||||||
|
|
|
|
| digital input is high. This causes heat in the | ||||||
|
|
|
|
| motor. |
|
|
|
| ||
P074 • | I2t motor derating | 0 - 1 | 0 = | Disabled |
|
|
|
|
|
|
|
|
| [1] | 1 = | Enabled. Causes an F074 trip if the motor I2t calculation reaches its | |||||||
|
|
|
| limit. The time taken to trip is dependent on the difference between | |||||||
|
|
|
| the overload current and the nominal motor current rating stored in | |||||||
|
|
|
| P083 - typically a 150% overload will result in a | |||||||
|
|
|
| minutes. |
|
|
|
|
|
|
|
|
|
| WARNING: | For | |||||||
|
|
|
|
| that a motor PTC is used to protect the motor from | ||||||
|
|
|
|
| overheating. |
|
|
|
| ||
P077 | Control mode | 0 - 2 | Controls the relationship between the speed of the motor and the | ||||||||
|
| [0] | voltage supplied by the inverter. |
|
|
|
| ||||
|
|
|
| 0 = Linear voltage/frequency. |
|
|
|
| |||
|
|
|
| Use this curve for synchronous motors or motors connected | |||||||
|
|
|
| in parallel. |
|
|
|
| |||
|
|
|
| 1 = Linear voltage/frequency with energy saving. |
|
|
|
| |||
|
|
|
| Output voltage is reduced at low load (not recommended for | |||||||
|
|
|
| dynamic loads). |
|
|
|
| |||
|
|
|
| 2 = Quadratic voltage/frequency relationship. |
|
|
|
| |||
|
|
|
| This is suitable for centrifugal pumps and fans. |
|
|
|
| |||
|
|
|
|
| VN |
|
|
|
|
| |
|
|
|
|
| Vmax |
|
|
|
|
| |
|
|
|
| VN (P084) | 0/1 |
|
|
|
|
| |
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
| 2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
| fN (P081) | f | ||||
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|