Siemens RDG400 manual 4.4Setpoints and sequence

Models: RDG400

1 42
Download 42 pages 12.55 Kb
Page 11
Image 11
4.4Setpoints and sequence

4.4Setpoints and sequence

In single-duct changeover applications the Comfort setpoints for heating and cooling sequence are the same (w).

In applications with electrical heater, radiator or heating / cooling coil the Comfort setpoint is at the heating sequence.

The start of the cooling sequence is linked to “Dead-zone” above the Comfort setpoint. The dead zone can be set via parameter P33.

The setpoints for Energy Saving and Protection mode are below the Comfort setpoints (heating) and above the Comfort setpoints (cooling).

They can be set via parameters P11, P12 (Energy Saving) and P65, P66 (Protection).

The control signal for air flow can be limited via parameters P63 and P64. See section 4.8.1.

To simplify the diagram below, only minimum limitation is shown.

 

 

 

 

 

 

 

 

 

wHeatProt

 

w

 

wCoolProt

 

 

wHeatEco

 

 

wCoolEco

T[°C]

3181D127

 

 

 

 

 

Comfort mode

 

 

 

Energy Saving / Protection mode

 

Application

Heating mode

Cooling mode

 

 

Heating mode

 

Cooling mode

 

 

Y

 

Y

 

 

Y

 

 

Y

 

 

Single duct

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WHeatEco T

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W

T

 

W

T

 

 

WHeatProt

 

 

 

WCoolEco

WCoolProt T

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Single duct

Y

 

Y

 

 

Y

 

 

Y

 

 

with min/max

 

 

 

 

 

 

 

limitation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W

T

 

W

T

 

 

WHeatProt

WHeatEco T

 

 

WCoolEco

WCoolProt T

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Comfort mode

 

Energy Saving

 

Protection mode

 

Application

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Single duct

 

Y

 

 

YE

 

 

YE

 

 

 

YE

 

with

 

 

 

 

 

 

 

Y

 

 

Y

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

electrical

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

heater

 

 

 

 

W

T

 

WHeatEco

WCoolEco

T

 

WHeatProt WCoolProtT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Y

 

 

YR

 

 

YR

 

 

 

YR

 

Single duct

 

 

 

 

 

 

 

Y

 

 

Y

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

with radiator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W

T

 

WHeatEco

WCoolEco

T

 

WHeatProt WCoolProtT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11 / 42

 

 

 

Siemens

RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation

CE1P3182en

Building Technologies

Functions

28 May 2009

Page 11
Image 11
Siemens RDG400 manual 4.4Setpoints and sequence