Siemens RDG400 manual Technical data

Models: RDG400

1 42
Download 42 pages 12.55 Kb
Page 38
Image 38
Technical data

Manual background Power supply

Outputs

Inputs

Operational data

8

 

 

 

Technical data

 

 

 

 

 

 

 

 

 

 

 

 

 

Operating voltage

 

SELV AC 24 V ± 20%

 

Frequency

 

50/60 Hz

 

 

 

Power consumption

 

Max. 2 VA

 

 

 

Control output Y10-G0

 

DC 0…10 V

 

 

 

 

Resolution

 

39 mV

 

 

 

 

Current

 

Max. ± 1 mA

 

 

 

Control output Y1, Y2-G

 

AC 24 V

 

 

 

 

Rating

 

Max. 1 A

 

 

 

Multifunctional inputs

 

 

 

 

 

 

X1-M / X2-M

 

 

 

 

 

 

 

 

 

Temperature sensor input

 

QAH11.1 (NTC)

 

 

 

 

 

Type

 

 

 

 

 

 

Digital input

 

Selectable (NO/NC)

 

 

 

 

 

Operating action

 

 

 

 

 

 

Contact sensing

 

DC 0…5 V, max. 5 mA

 

 

D1-GND

 

Selectable (NO/NC)

 

 

 

 

 

Operating action

 

 

 

 

 

 

Contact sensing

 

SELV DC 6…15 V, 3…6 mA

 

 

Function input

 

Selectable

 

 

 

 

 

 

 

External temperature sensor, changeover

 

 

 

 

 

 

 

 

sensor, operating mode switchover contact,

 

 

 

 

 

 

 

 

dewpoint monitor contact, enable electrical

 

 

 

 

 

 

 

 

heater contact, fault contact

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Switching differential, adjustable

 

2 K (0.5...6 K)

 

 

Heating mode

(P30)

 

 

Cooling mode

(P31)

1 K (0.5...6 K)

 

 

Setpoint setting and range

 

21 °C

(5...40 °C)

 

 

 

 

 

Comfort mode

(P08)

 

 

 

 

 

 

 

 

 

Energy Saving mode

(P11-P12)

15 °C/30 °C (OFF, 5...40

 

 

 

 

 

Protection

(P65-P66)

°C)

(OFF, 5...40 °C)

 

 

 

 

 

 

 

8 °C/OFF

 

Multifunctional inputs X1 / X2 / D1

 

Selectable

 

 

 

 

Input X1

 

Ext. temperature sensor

 

 

 

 

 

 

 

(P38=1)

 

 

 

 

Input X2

 

Changeover sensor

 

 

 

 

 

 

 

(P40=2)

 

 

 

 

Input D1

 

Operating mode switchover

 

 

 

 

 

 

 

(P42=3)

 

 

 

Built-in room temperature sensor

 

0…49 °C

 

 

 

 

Measuring range

 

 

 

 

 

Accuracy at 25 °C

 

< ± 0.5 K

 

 

 

 

Temperature calibration range

 

± 3.0 K

 

 

 

Settings and display resolution

 

0.5 °C

 

 

 

 

Setpoints

 

 

 

 

 

Current temperature value displayed

 

0.5 °C

 

 

38 / 42

Siemens

RDG100…/RDG110…/RDG140.../RDG160… Basic Documentation

CE1P3182en

Building Technologies

Technical data

28 May 2009

Page 38
Image 38
Siemens RDG400 manual Technical data