4.12.2Parameters Expert level, diagnostics & test

Parameter

Name

Factory setting

Range

 

 

 

 

 

 

 

 

 

 

RDG400

 

Expert level

 

 

 

 

 

 

 

P30

P-band / Switching differential in heating mode

2 K

0.5 … 6 K

 

 

 

 

 

 

 

 

 

 

P31

P-band / Switching differential in cooling mode

1 K

0.5 … 6 K

 

 

 

 

 

 

 

 

 

 

P32

P-band / Switching differential for radiator

2 K

0.5 … 6 K

 

 

 

 

 

 

 

 

 

 

P33

Dead zone in Comfort mode

2 K

0.5 … 5 K

 

 

 

P34

Setpoint differential (wD)

2 K

0.5 … 5 K

 

 

 

P35

Integral time

5 min

0…10 min

 

 

 

P36

Heating / cooling changeover switching point

16 °C

10…25 °C

 

 

 

 

cooling (X1/X2)

 

 

 

 

 

 

 

P37

Heating / cooling changeover switching point

28 °C

27…40 °C

 

 

 

 

heating (X1/X2)

 

 

 

 

 

 

 

P38

Functionality of X1

1: = Ext. sensor

0

= --- (no function)

 

 

0..6

 

 

 

1

= Room temp ext / Return temp (AI)

 

 

 

 

2

= H/C changeover (AI/DI)

 

 

 

 

 

3

= Operating mode contact [DI)

 

 

 

 

 

4

= Dew point sen. (DI)

 

 

 

 

 

5

= Enable electric heater (DI)

 

 

 

 

 

6

= Fault input (DI)

 

 

 

 

 

 

 

 

 

 

 

P39

Operating action of X1 if digital input

0 (N.O.)

0

= Normally open

/ Open

 

 

 

 

 

1

= Normally closed

/ Closed

 

 

P40

Functionality of X2

2 = H/C changeover

0

= --- (no function)

 

 

0..6

 

 

 

1

= Room temp ext / Return temp (AI)

 

 

 

 

2

= H/C changeover (AI/DI)

 

 

 

 

 

3

= Operating mode contact [DI)

 

 

 

 

 

4

= Dew point sen. (DI)

 

 

 

 

 

5

= Enable electric heater (DI)

 

 

 

 

 

6

= Fault input (DI)

 

 

 

 

 

 

 

 

 

 

 

P41

Operating action of X2 if digital input

0 (N.O.)

0

= Normally open

/ Open

 

 

 

 

 

1

= Normally closed

/ Closed

 

 

P42

Functionality of D1

3 = Op. mode

0

= --- (no function)

 

 

0..6

 

 

changeover

2

= H/C changeover (DI)

 

 

 

 

3

= Operating mode contact [DI)

 

 

 

 

 

4

= Dew point sen. (DI)

 

 

 

 

 

5

= Enable electric heater (DI)

 

 

 

 

 

6

= Fault input (DI)

 

 

 

 

 

 

 

 

 

 

P43

Operating action of D1 if digital input

0 (N.O.)

0

= Normally open / Open

 

 

 

 

 

1

= Normally closed / Closed

 

 

P44

Running time of Y1/Y2 output

150 s

20…300 sec

 

 

 

 

(only when modulating PI control)

 

 

 

 

 

 

 

P46

Output Y1/Y2 (if not parameterized as 3-pos.)

ON/OFF (1)

1

= 2-position

 

 

 

 

 

 

2

= PWM

 

 

 

P51

Floor heating limit temperature

OFF

OFF, 10..50 °C

 

 

 

 

 

 

 

 

 

 

P63

Minimum output limitation air flow signal

0%

0…P64 (%)

 

 

 

 

 

 

 

 

 

 

P64

Maximum output limitation air flow signal

100%

P63…100 (%)

 

 

 

 

 

 

 

 

 

P65

Protection heating setpoint

8 °C

OFF, 5 … W Cool Prot;

 

 

 

 

 

(W Cool Prot = 40 °C max)

 

 

P66

Protection cooling setpoint

OFF

OFF, W Heat Prot … 40;

 

 

 

 

 

(W Heat Prot = 5 °C min.)

 

 

P68

Prolong Comfort period

OFF

OFF; 15 ... 360 min

 

 

 

 

 

 

 

 

 

 

P69

Temporary setpoint Comfort

OFF

OFF = Disabled

 

 

 

 

(see also Comfort setpoint P08)

 

ON = Enable

 

 

 

P71

Reload factory settings

OFF

OFF

= Disabled

 

 

 

 

 

 

ON

= Reload start

 

 

 

Note P46: Setting to 2-position or 3-position is done with DIP 4