Siemens RDG400 manual Button lock

Models: RDG400

1 42
Download 42 pages 12.55 Kb
Page 16
Image 16
Button lock

Button lock

If the button lock function is enabled by parameter P14, then the buttons will be

 

locked or unlocked by pressing the right button for 3 sec.

 

If “Auto lock” is configured, then the thermostat will automatically lock the buttons

 

10 sec after the last adjustment.

Operating mode switchover contact (Window contact)

Extended Comfort mode (operating mode switchover contact closed)

Temporary timer for extension of presence / absence

The thermostat can be forced into Energy Saving mode, e.g. when a window is opened. The window contact can be connected to digital input D1 (or multifunctional input X1, X2). Set parameter P42 (P38, P40) to 3.

The left button switches the operating mode from Energy Saving to Comfort for the period preset in P68, if the following conditions are fulfilled:

The operating mode switchover contact is closed (connected to input X1, X2, D1, parameter P38, P40, P42 set to 3)

Parameter P68 (extend Comfort period) is greater than 0

During the temporary Comfort mode extension, timer symbol Manual background appears.

If parameter P68 (extend Comfort period) = 0, extended Comfort cannot be activated; pressing the left button will show “OFF” (blinking 3 times)

The current operating mode can be forced temporarily into Comfort or Energy Saving / Protection mode. The time period is adjusted via the rotary knob:

Extend presence: Set the device to Comfort mode for the selected time period

Extend absence: Set the device to Energy Saving / Protection mode for the selected time period

To activate the function, keep the left button pressed and, within 3 seconds, turn the rotary knob

clockwise for extended presence

counterclockwise for extended absence The rotary knob adjusts the time period:

Extend presence: 0.00…+9:30 in steps of 30 minutes; symbol Manual background appears

Extend absence: 0.00…–9:30 in steps of 30 minutes; symbol Manual background or Manual background appears

During the extended presence / absence period, timer symbol Manual background appears.

Function

User operating mode

Operating

Function

Operating mode

Operating mode at

selection

mode when

 

during function

the end of function

 

activating

 

 

 

 

function

 

 

 

Comf

Extension

Comf

Prot

Comf

Absence

Prot

Comf

Prot

Not available

-

-

Comf

Extension

Comf

Eco

Comf

Absence

Eco

Comf

 

Eco

Extension

Comf

Eco

 

Eco

Absence

Eco

Comf

 

Prot

Not available

-

-

16 / 42

Siemens

RDG100…/RDG110…/RDG140.../RDG160… Basic Documentation

CE1P3182en

Building Technologies

Functions

28 May 2009

Page 16
Image 16
Siemens RDG400 manual Button lock