Siemens RDG400 manual Functions, 4.1Temperature control

Models: RDG400

1 42
Download 42 pages 12.55 Kb
Page 8
Image 8
4 Functions

4 Functions

4.1Temperature control

General note

Setting of the control parameters (P01 etc., mentioned throughout the document) is

 

described in section 4.12.

The thermostat acquires the room temperature via built-in sensor, external room temperature sensor (QAA32), or external return air temperature sensor (QAH11.1), and maintains the setpoint by issuing actuator control commands to heating and/or cooling equipment. The following control outputs are available:

Modulating PI / P control with DC 0 … 10 V control output

Modulating PI / P control with 3-position control output

Modulating PI / P control with PWM output

On/off control (2-position)

 

 

 

 

 

The switching differential or proportional band is 2 K for heating and 1 K for cooling

 

 

 

 

 

(adjustable via parameters P30 and P31).

 

 

 

 

 

 

 

The integral action time for continuous PI control is 5 minutes (adjustable via

 

 

 

 

 

parameter P35).

 

 

 

 

 

 

 

 

Display

The display shows the acquired room temperature or the Comfort setpoint, selecta-

 

 

 

 

 

ble via parameter P06. The factory setting displays the current room temperature.

 

 

 

 

 

Use parameter P04 to display the room temperature or setpoint in °F rather than

 

 

 

 

 

°C as needed.

 

 

 

 

 

 

 

 

/

 

 

 

If the thermostat is used in a system with manual heating/cooling changeover

 

 

 

 

 

 

 

 

 

(P01=2), the heating and cooling

 

 

 

symbols on the display show the terminal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

unit status. Thus, the symbols are displayed even when the thermostat operates in

 

 

 

 

 

the neutral zone. For all other cases, the heating and cooling

 

 

 

symbols are

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

displayed when the heating or cooling output is energized.

 

 

Concurrent display of

Concurrent display of the current temperature or setpoint in °C and in °F

°C and °F

(parameter P07) is possible.

 

 

 

 

 

 

 

 

8 / 42

Siemens

RDG100…/RDG110…/RDG140.../RDG160… Basic Documentation

CE1P3182en

Building Technologies

Functions

28 May 2009

Page 8
Image 8
Siemens RDG400 manual Functions, 4.1Temperature control