4.6Additional features

Output signal inversion

Min / Max air flow

The output signals DC 0…10V can be inverted by means of DIP switch 4 (see section 4.7.3).

To ensure a minimum or maximum supply air volume, the output signal for the air flow (DC 0...10V or 3-position) can be limited to a minimum value via parameter P63 and to a maximum value via parameter P64.

Both values can be set between 0% and 100%.

 

 

Changeover

 

T

Y10

 

 

 

XpH

XpC

 

Y10

 

H

C

100%

 

 

w

 

 

 

 

Vmax

 

 

 

max

XpH

 

 

 

 

XpC

 

 

 

 

 

Vmin

 

 

 

 

Vmin

 

 

 

min

Vmax

 

 

 

 

0%

 

 

W

TR [°C]

 

 

 

 

 

Room temperature Control output

Room temperature setpoint Proportional band Heating Proportional band Cooling Minimum limitation air flow Maximum limitation air flow

If Vmin is not set >0, then a minimum air flow of Vmin is assured in Comfort and Energy Saving modes. In Protected mode, Vmin is 0.

Comfort or Energy Saving mode with Vmin

Y

 

 

 

100%

H

 

C

Vmax

 

 

max

 

 

 

Vmin

 

YV

 

 

min

 

 

 

0%

SpHComf/Eco

SpCComf/Eco

TR [°C]

 

Protection mode (Vmin = 0)

Y

 

 

 

100%

H

 

C

Vmax

 

 

max

 

 

 

Vmin

 

 

YV

 

 

min

 

 

 

0%

SpHProt

SpCProt

TR [°C]

 

Automatic H/C

The water temperature acquired by the changeover sensor (QAH11.1 + ARG86.3)

changeover

is used to change over from heating to cooling mode and vice-versa. When the

 

water temperature is above 28 °C (parameter P37), the thermostat changes over to

 

heating mode, and to cooling mode when below 16 °C (parameter P36).

 

If the water temperature is between the 2 changeover points immediately after

 

power-up, the thermostat starts in heating mode.

 

The water temperature is acquired at 30-second intervals and the operating state is

 

updated accordingly.

 

 

 

 

 

 

M

 

Tw[°C]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

28

 

 

MOperating mode Tw Water temperature

Cooling mode Heating mode

Remote heating/

The QAH11.1 cable temperature sensor for automatic heating/cooling changeover

cooling changeover

can be replaced by an external switch for manual, remote changeover:

 

14 / 42

 

 

 

 

 

Siemens

RDG100…/RDG110…/RDG140.../RDG160… Basic Documentation

CE1P3182en

Building Technologies

Functions

28 May 2009

Page 14
Image 14
Siemens RDG400 manual Additional features