Single duct

 

 

Single duct,

In single duct applications, the controller controls an actuator (valve, damper, VAV

heating or cooling

system, etc)

 

in heating/cooling mode with changeover (automatic or manual),

 

heating only mode,

 

or cooling only mode.

Cooling only is factory set (P01=1).

The output signal for the air flow can be limited to a minimum and maximum value if required (see section 4.6 "additional features").

Modulating control 3-position, PWM or DC 0 … 10 V

The diagram below shows the control sequence for continuous PI control.

Heating only (P01 = 0)

 

Y10

XpH

 

 

H

 

100%

 

 

 

 

 

Vmax

 

 

max

 

 

 

Vmin

 

 

min

 

 

 

0%

 

W

TR [°C]

 

 

Changeover (P01 = 2, 3)

 

 

 

Changeover

 

Y10

XpH

XpC

 

 

H

C

100%

 

 

 

 

 

 

Vmax

 

 

 

max

 

 

 

 

Vmin

 

 

 

min

 

 

 

 

0%

 

W

 

TR [°C]

 

 

 

Cooling only (P01 = 1)

 

Y10

 

XpC

C

100%

 

Vmax

max

 

Vmin

min

 

0%

 

W

TR [°C]

T[°C]

Room temperature

XpH

Proportional band “Heating”

w

Room temperature setpoint

XpC

Proportional band “Cooling”

Y10

Control command “Valve”

Vmin

Min. limitation for output

 

 

Vmax

Max. limitation for output

Note The diagrams show the PI controller’s proportional part only.

Setting the sequence and the control outputs

Refer to sections 4.5 (applications), 4.7.1 (sequences) and 4.7.3 (outputs).

 

 