4.12.1Parameters Service level

Parameter

Name

Factory setting

Range

 

 

 

 

 

 

 

 

RDG400

 

Service level

 

 

 

 

 

 

P01

Control sequence

When 2-pipe /

0

= Heating only

 

 

 

 

2-stage:

1

= Cooling only

 

 

 

 

1

= Cooling only

2

= H/C changeover manual

 

 

 

 

When 4-pipe:

3

= H/C changeover auto

 

 

 

 

4

= H and C

4

= Heating and Cooling

 

 

 

 

 

 

 

 

 

 

P02

User operating mode profile (mode button)

1

 

1

= (Auto) - Comfort - Protection

 

 

 

 

 

 

2

= (Auto) - Comfort - E Saving - Prot

 

 

P04

Selection of °C or °F

0

(°C)

0

= Degrees Celsius (°C)

 

 

 

 

 

 

1

= Degrees Fahrenheit (°F)

 

 

P05

Sensor calibration (intern, extern)

0

K

– 3 ... 3 K

 

 

P06

Standard temperature display

0

 

0

= Room Temperature

 

 

 

 

 

 

1

= Setpoint

 

 

P07

Display info line

0

 

0

= --- (No display)

 

0..1

 

(2nd line of LCD)

 

 

1

= °C and °F

 

 

P08

Comfort setpoint

21 °C

5

... 40 °C

 

 

P09

Minimum setpoint in Comfort mode

5

°C

5

... 40 °C

 

 

P10

Maximum setpoint in Comfort mode

35 °C

5

... 40 °C

 

 

P11

Energy Saving heating setpoint

15 °C

OFF, 5 ... WcoolE-saving;

 

 

 

 

 

 

(WcoolE-saving = 40 °C max)

 

 

P12

Energy Saving cooling setpoint

30 °C

OFF, WHeatE-saving ... 40 °C;

 

 

 

 

 

 

(WHeatE-saving = 5 °C min)

 

 

P14

Button lock function

0

 

0

= Unlocked

 

 

 

 

 

 

1

= Auto locked

 

 

 

 

 

 

2

= Manual locked

 

 

 

 

 

 

 

 

 

 