4.9Multifunctional input, Digital input

The thermostat offers two multifunctional inputs X1 and X2 and a digital input D1. A sensor of type NTC like QAH11.1 (AI, analog input) or a switch (DI, digital input) can be connected to the input terminals. The functionality of the inputs can be configured via parameters P38 for X1, P40 for X2, and P42 for D1.

#

Function of input

Description

Type

Type

 

 

 

X1/X2

DI

0

Not used

No function.

--

--

1

External/Return

Sensor input for external room temperature sensor or

AI

 

 

air temp.

return air temperature sensor to measure the current

 

 

 

 

room temperature, or floor heating temperature

 

 

 

 

sensor to limit the heating output.

 

 

 

 

Note: The room temperature is measured by the built-

 

 

 

 

in sensor if the floor heating limitation function is

 

 

 

 

enabled via parameter P51.

 

 

2

Heat/cool

Sensor input for automatic heating / cooling

AI/(DI)

DI

 

changeover

changeover function.

 

 

 

 

A switch can also be connected rather than a sensor

 

 

 

 

(switch closed = cooling, see section 4.6).

 

 

3

Operating mode

Digital input to switch over the operating mode to

DI

DI

 

switchover

Energy Saving.

 

 

 

 

If the operating mode switchover contact is active,

 

 

 

 

user operations are ineffective and “OFF” is displayed.

 

 

4

Dewpoint monitor

Digital input for a dewpoint sensor to detect

DI

DI

 

 

condensation. Cooling is stopped if condensation

 

 

 

 

occurs.

 

 

5

Enable electrical

Digital input to enable/disable the electrical heater via

DI

DI

 

heater

remote control.

 

 

6

Fault

Digital input to signal a fault.

DI

DI

 

 

If the input is active, “ALx” is displayed

 

 

 

 

(Alarm x, with x = 1 for X1, x = 2 for X2, x = 3 for D1).

 

 

 

 

Note: Fault displays do not influence the thermostat's

 

 

 

 

operation. They merely represent a visual signal.

 

 

 

 

Example: dirty air filter

 

 

Operational action can be changed between normally open (N.O.) and normally closed (N.C.) via parameter P39, P41 (or P43 if it is a digital input).

Each input X1, X2 or D1 must be configured with a different function (1 … 5). Exception: one or two or three inputs may be configured as alarm inputs (6)

X1 is factory-set to “External sensor” (1), X2 to “Heating/Cooling changeover” (2), and D1 to Operating mode changeover (3).

For more information see section 4.5 “Applications”.

26 / 42

Siemens

RDG100…/RDG110…/RDG140.../RDG160… Basic Documentation

CE1P3182en

Building Technologies

Functions

28 May 2009

Page 26
Image 26