Siemens RDG400 Siemens, CE1P3182en, Building Technologies, Functions, 28 May, Parameter, Name

Models: RDG400

1 42
Download 42 pages 12.55 Kb
Page 31
Image 31
Manual background

Parameter

d01

d02

d03

d04

d05

Name

Factory setting

Range

 

 

 

Diagnostics & test

 

 

 

 

 

 

 

 

 

RDG400

 

 

 

 

 

 

 

 

 

 

Application type

Diagnostics

0:= --- (No application)

 

 

 

 

1:= Single-duct

 

 

 

 

2:= Single-duct with el. heater

 

 

 

 

3:= Single-duct with radiator

 

 

 

 

4:= Single-duct with h/c coil

 

 

X1 status

Diagnostics

0

= Not activated (for DI)

 

 

 

 

1

= activated (DI)

 

 

 

 

0…49 °C = cur. temp. value (for AI)

 

 

 

 

00

 

 

 

 

= HC input short

 

 

 

 

 

 

 

 

 

 

 

 

 

100

 

= HC input open

 

 

X2 status

Diagnostics

0

= Not activated (for DI)

 

 

 

 

1

= activated (DI)

 

 

 

 

0…49 °C = cur. temp. value (for AI)

 

 

 

 

00

 

 

 

 

= HC input short

 

 

 

 

 

 

 

 

 

 

 

 

100

 

 

 

= HC input open

 

 

D1 status

Diagnostics

0

= Not activated (for DI)

 

 

 

 

1

= activated (DI)

 

 

 

 

00

 

 

 

 

= HC input short

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100 = HC input open

 

 

 

 

 

 

 

 

 

Test mode for checking the Y1/Y2

---

“---“ = no signal on outputs Y1 and Y2

 

 

actuator direction

 

OPE = output Y1 forced open

 

 

(press left button to escape)

 

CLO = output Y2 forced closing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

31 / 42

 

 

 

Siemens

RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation

CE1P3182en

Building Technologies

Functions

28 May 2009

Page 31
Image 31
Siemens RDG400 Siemens, CE1P3182en, Building Technologies, Functions, 28 May, Parameter, Name, Factory setting, Range