Parameter

d01

d02

d03

d04

d05

Name

Factory setting

Range

 

 

 

Diagnostics & test

 

 

 

 

 

 

 

 

 

RDG400

 

 

 

 

 

 

 

 

 

 

Application type

Diagnostics

0:= --- (No application)

 

 

 

 

1:= Single-duct

 

 

 

 

2:= Single-duct with el. heater

 

 

 

 

3:= Single-duct with radiator

 

 

 

 

4:= Single-duct with h/c coil

 

 

X1 status

Diagnostics

0

= Not activated (for DI)

 

 

 

 

1

= activated (DI)

 

 

 

 

0…49 °C = cur. temp. value (for AI)

 

 

 

 

00

 

 

 

 

= HC input short

 

 

 

 

 

 

 

 

 

 

 

 

 

100

 

= HC input open

 

 

X2 status

Diagnostics

0

= Not activated (for DI)

 

 

 

 

1

= activated (DI)

 

 

 

 

0…49 °C = cur. temp. value (for AI)

 

 

 

 

00

 

 

 

 

= HC input short

 

 

 

 

 

 

 

 

 

 

 

 

100

 

 

 

= HC input open

 

 

D1 status

Diagnostics

0

= Not activated (for DI)

 

 

 

 

1

= activated (DI)

 

 

 

 

00

 

 

 

 

= HC input short

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100 = HC input open

 

 

 

 

 

 

 

 

 

Test mode for checking the Y1/Y2

---

“---“ = no signal on outputs Y1 and Y2

 

 

actuator direction

 

OPE = output Y1 forced open

 

 

(press left button to escape)

 

CLO = output Y2 forced closing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

31 / 42

 

 

 

Siemens

RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation

CE1P3182en

Building Technologies

Functions

28 May 2009

Page 31
Image 31
Siemens RDG400 manual Diagnostics & test