4.7.3Control outputs overview

(setting via DIP 4 / 5 and parameters P46 / P47)

Control outputs

Application

Single duct

Single duct and electrical heater

Single duct and radiator / floor heating

Single-duct heating / cooling coil

ON/OFF (2-position)

Modulating PWM (2-position)

Modulating 3-position

Modulating DC 0 … 10 V

The function of the control outputs is set via DIP switches 4 and 5:

ON

 

 

 

 

 

ON

 

 

 

 

 

ON

 

 

 

 

 

ON

 

 

 

 

 

OFF

 

 

 

 

 

OFF

 

 

 

 

 

OFF

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

4

5

1

2

3

4

5

1

2

3

4

5

1

2

3

4

5

3181D101

DIP 4:

 

Y10 =

0 … 10 V

0 … 10 V

10 … 0 V inverted

10 … 0 V inv

DIP 5:

Y1 / Y2 =

2-position

3-position

2-position

3-position

Note

Y1, Y2:

 

 

 

 

If 2-position is selected, the factory setting is on/off.

If you want PWM (pulse width modulation), set parameter P46 to 2 = PWM.

P47:

0 = VAV box DC 0 … 10 V control signal

1 = VAV box : 3-position control signal

For details concerning connection of peripheral devices and setting of the DIP switches please refer to the mounting instructions, M3182 [3]:

18 / 42