4.7.7Single duct with heating / cooling coil

Water coil valve in cooling mode

Water coil valve in heating mode

Control sequence

In single duct applications with heating / cooling coil, the controller controls an actuator (damper, VAV system, etc.) plus a reheating / cooling water coil.

The output signal for the air flow can be limited to a minimum and maximum value if required (see section 4.6 "additional features").

The thermostat controls the reheating / cooling water valve either in heating / coo- ling mode with changeover (automatic or manual), heating only, or cooling only. Cooling only is factory set (P01=01).

If the room temperature is above the setpoint for cooling, the valve will receive an OPEN command and the air flow signal starts to rise in order to maintain the room temperature.

If the room temperature drops below the setpoint for heating, then the valve will receive an OPEN command.

The diagram below shows the control sequence for continuous PI control in Comfort mode.

On/off heating / cooling coil

Y

XpC

 

100%

C

 

 

 

Vmax

 

max

 

 

Vmin

YV

 

min

 

 

 

0%

 

 

TR [°C]

Changeover water

Modulating heating / cooling coil

Y

XpC

 

100%

C

 

 

 

Vmax

 

max

 

 

Vmin

YV

 

min

 

 

 

0%

 

 

TR [°C]

Changeover water

Y

SDH

SDC

 

H

C

ON

 

 

 

 

YHC

HCY

 

 

 

 

OFF

W

 

 

 

dz

 

 

 

TR [°C]

 

 

 

Y

H XpH

100%

0%W

dz

XpC C

YHC

TR [°C]

Y

Output signal

TR

Room temperature

WComfort setpoint

H Heating sequence

C Cooling sequence

YV

Volume flow rate

XpH

Proportional band heating

XpC

Proportional band cooling

Vmin

Minimum volume output

Vmax

Maximum volume output

Note: The diagrams show the PI controller's proportional part only.

Setting the sequence and the control outputs

Refer to sections 4.5 (applications), 4.7.1 (sequences) and 4.7.3 (outputs).

22 / 42

Siemens

RDG100…/RDG110…/RDG140.../RDG160… Basic Documentation

CE1P3182en

Building Technologies

Functions

28 May 2009

Page 22
Image 22
Siemens RDG400 manual Single duct with heating / cooling coil, Control sequence, Modulating heating / cooling coil