4.7.5

Single duct with electrical heater

 

 

Single duct with electrical

In single duct applications with electrical heater, the thermostat controls a valve

heater

plus an auxiliary electrical heater. Parameter P01 is not available.

 

The output signal for the air flow can be limited to a minimum and maximum value

 

if required (see section 4.6 "additional features").

Electrical heating,

The air flow starts to rise when the acquired room temperature is above "setpoint"

active in cooling mode

+ "dead zone".

 

The electrical heater receives an ON command when the acquired room

 

temperature drops below “setpoint” – “dead zone” (= “setpoint for electrical

 

heater”).

 

Digital input “Enable

Remote enabling/disabling of the electrical heater is possible via input X1, X2, or

electrical heater”

D1 for overheat protection, tariff regulations, energy saving etc.

 

Input X1, X2, or D1 must be commissioned accordingly (parameter P38, P40, P42).

 

See section 4.9 “Multifunctional input”.

Caution

In case of insufficient air flow, the thermostat cannot protect the electrical heater

 

against overtemperature. That is why the electrical heater must feature a separate

 

safety device (thermal cutout).

Sequences

ON/OFF electrical heater

Y

 

XpC

C

100%

 

Vmax

max

 

YV

 

Vmin

 

min

 

0%

 

TR [°C]

Y

SDH

ON

YE

Modulating electrical heater

Y

XpC

 

100%

C

 

 

 

Vmax

 

max

 

 

Vmin

YV

 

min

 

 

 

0%

TR [°C]

 

Y

XpH

100%

YE

OFF

W

dz

TR [°C]

 

0%

 

 

W

 

 

 

 

dz

 

TR [°C]

Y

Output signal

TR

Room temperature

WEffective setpoint Comfort

H Heating sequence

C Cooling sequence

YV

Volume flow rate

YE

Electrical heater

XpH

Proportional band heating

XpC

Proportional band cooling

Vmin

Minimum volume output

Vmax

Maximum volume output

Note: The diagrams show the PI controller's proportional part only.

Setting the sequence and the control outputs

Refer to sections 4.5 (applications), 4.7.1 (sequences) and 4.7.3 (outputs).

20 / 42

Siemens

RDG100…/RDG110…/RDG140.../RDG160… Basic Documentation

CE1P3182en

Building Technologies

Functions

28 May 2009

Page 20
Image 20
Siemens RDG400 manual Single duct with electrical heater, Sequences, Modulating electrical heater