Control outputs

 

 

4.8

 

Control outputs

 

 

 

 

 

 

 

 

 

 

 

 

 

Overview of control

Different control output signals are available depending on the configuration of

 

outputs

thermostat via DIP switches 4 & 5, and parameters P46 & P47.

 

 

 

 

Control output

 

Modulating

 

2-position

 

2-position

 

Modulating

 

 

 

 

 

 

 

 

Product No.

 

 

DC 0 … 10 V

 

on/off

 

PWM

 

3-position

 

 

 

 

 

 

 

 

 

 

 

 

 

RDG400

 

 

Y10

 

Y1

 

Y1

 

Y1/Y2

 

 

 

 

 

 

 

 

 

 

 

(1 x / )

 

DC 0..10 V control signal

3-posotion control signal

Synchronization

4.8.1Control output for air flow

The demand calculated by the PI control from the current room temperature and setpoint is provided to the valve actuator as a continuous DC 0...10 V signal via output Y10.

A 3-position control output for a damper has 2 control signals, one for the “opening” command and one for the “closing” command. The thermostat has an internal stroke model to calculate the position of the actuator. Therefore the running time from the fully closed to the fully open position has to be adjusted via parameter P44 (from 20…300sec; factory setting is 150 seconds).

In single-duct applications, a closing synchronization is done to readjust the internal stroke model to the real position of the actuator.

1.When the controller starts up, a closing signal (actuator running time + 150% = 2.5 x running time) is delivered to ensure the actuator will be fully closed and synchronized with the control algorithm.

2.Each time the controller calculates the position fully closed, the actuator’s running time is extended + 150% to ensure the right position of the actuator.

3.When the actuator has reached the position calculated by the controller, a waiting time of 30 seconds is observed in order to stabilize the outputs.

Note: opening synchronization is available for valve outputs only.

 

 