Siemens RDG400 manual Engineering, 6.1Connection terminals

Models: RDG400

1 42
Download 42 pages 12.55 Kb
Page 35
Image 35
6 Engineering

6 Engineering

6.1Connection terminals

G X1 M X2

D1 GND

G0

SELV

G, G0 Operating voltage AC 24 V

Y10/G0 Control output for DC 0…10 V actuator

Y1/G, Y2/G Control output for 2-position, PWM or 3-position actuators

X1, X2 Multifunctional input for temperature sensor (e.g. QAH11.1) or potential-free switch

Factory setting:

-X1 = external room temperature sensor

-X2 = sensor or switch for automatic heating / cooling changeover

M

Measuring neutral for sensor and switch

D1, GND

Multifunctional input for potential-free switch.

 

Factory setting: Operating mode switchover contact

 

 

35 / 42

 

 

 

Siemens

RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation

CE1P3182en

Building Technologies

Engineering

28 May 2009

Page 35
Image 35
Siemens RDG400 manual Engineering, 6.1Connection terminals