Environmental conditions

Standards

General

Operation

As per IEC 721-3-3

 

Climatic conditions

Class 3K5

 

Temperature

0...50 °C

 

Humidity

<95% r.h.

Transport

As per IEC 721-3-2

 

Climatic conditions

Class 2K3

 

Temperature

25... 60 °C

 

Humidity

<95% r.h.

 

Mechanical conditions

Class 2M2

Storage

As per IEC 721-3-1

 

Climatic conditions

Class 1K3

 

Temperature

25... 60 °C

 

Humidity

<95% r.h.

 

 

conformity

 

 

 

 

 

EMC directive

2004/108/EC

 

 

N474 C-tickconformity to

 

 

EMC emission standard

AS/NSZ 4251.1:1999

 

 

 

 

 

 

 

 

Reduction of hazardous substances

2002/95/EC

 

 

 

 

 

Product standards

As per EN 60730–1

 

Automatic electrical controls for household and

 

similar use

As per EN 60730–2-9

 

Special requirements for temperature-dependent

 

controls

2.B (micro-disconnection on

 

Electronic control type

 

 

 

 

operation)

 

 

Electromagnetic compatibility

As per IEC/EN 61000-6-3

 

Emissions

 

Immunity

As per IEC/EN 61000-6-2

Safety class

III as per EN 60730

Pollution class

Normal

Degree of protection of housing

IP30 as per EN 60529

Connection terminals

Solid wires or prepared

 

 

 

 

stranded wires

 

 

 

 

1 x 0.4…2.5 mm2

 

 

 

 

or 2 x 0.4…1.5 mm2

Housing front color

RAL 9003 white

Weight

0.350 kg

 

 

 

 

 

 

 

39 / 42

 

 

 

Siemens

RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation

CE1P3182en

Building Technologies

Technical data

28 May 2009

Page 39
Image 39
Siemens RDG400 manual