Siemens RDG400 External / return air, temperature sensor, Floor heating, limitation function

Models: RDG400

1 42
Download 42 pages 12.55 Kb
Page 15
Image 15
External / return air

 

 

X2

T

X2

Contact open

heating mode

 

 

 

 

 

M

M

 

 

 

 

 

 

 

 

QAH11.1

Contact closed

cooling mode

 

 

 

 

3076Z03

 

 

 

 

 

 

 

 

 

 

 

T °C

 

 

 

 

 

 

 

 

The sensor or switch can be connected to the input terminal X2 (factory setting) or

 

X1 or D1 (switch only), depending on the commissioning of the inputs (P38, P40,

 

P42).

 

 

 

 

 

 

 

 

See also section 4.9 “Multifunctional input”.

 

 

 

 

 

External / return air

The thermostat acquires the room temperature via built-in sensor, external room

temperature sensor

temperature sensor (QAA32), or external return air temperature sensor (QAH11.1)

 

connected to multifunctional input X1 or X2.

 

 

 

 

 

 

Inputs X1 or X2 need to be commissioned accordingly. See section 4.9 “Multi-

 

functional input”.

 

 

 

 

 

 

 

Floor heating

Application "Single duct and radiator" can also be used for floor heating.

Floor heating

The temperature should be limited for two reasons: comfort and protection of the

limitation function

floor. It is only available with application "Single duct and radiator".

 

 

 

 

 

The floor temperature sensor, connected to multifunctional input X1 or X2,

 

 

 

 

 

measures the floor temperature. If the temperature exceeds the parameterized limit

 

 

 

 

 

(parameter P51), the heating valve is fully closed until the floor temperature drops

 

 

 

 

 

to 2K below the parameterized limit.

 

 

 

 

 

 

 

 

 

This function is factory-set to OFF (disabled).

 

 

 

 

 

 

 

 

Input X1 or X2 must be commissioned accordingly (P38 or P40 = 1).

 

 

 

 

 

See section 4.9 “Multifunctional input”.

 

 

 

 

Recommended values

Living rooms:

 

 

 

 

for P51:

 

up to 26 °C for long term presence, up to 28 °C for short time presence

 

 

 

 

 

Bath rooms:

 

 

 

 

 

 

 

 

 

 

 

up to 28 °C for long term presence, up to 30 °C for short time presence

 

 

 

 

 

The table below shows the relation between parameter, temperature source and

 

 

 

 

 

temperature display:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter P51

 

External temp.

 

Source for display of room

 

Output control according

Floor temp. limit

 

 

 

 

sensor available

 

temperature

 

to

function

 

 

 

 

 

 

 

 

 

 

OFF

No

 

 

Built-in sensor

 

Built-in sensor

Not active

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Yes

 

 

External temp. sensor

 

External temp. sensor

Not active

 

 

 

 

 

 

 

 

 

 

 

 

 

10...50˚C

No

 

 

Built-in sensor

 

Built-in sensor

Not active

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10…50˚C

Yes

 

 

Built-in sensor

 

Built-in sensor + limit by

Active

 

 

 

 

 

external sensor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dewpoint monitoring

Dewpoint monitoring is essential to prevent condensation on the cooling coil.

 

 

 

 

 

It helps avoid associated damage to the building.

 

 

 

 

 

 

 

 

A dewpoint sensor with a potential-free contact is connected to multifunctional input

 

 

 

 

 

X1, X2 or D1. If there is condensation, the cooling valve is fully closed until no

 

 

 

 

 

more condensation is detected, and the cooling output is disabled temporarily.

 

 

 

 

 

The condensation symbol is displayed during temporary override.

 

 

 

 

 

The input must be commissioned accordingly (P38, P40, P42).

 

 

 

 

 

 

 

 

See section 4.9 “Multifunctional input”.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15 / 42

 

 

 

 

 

 

 

 

 

 

 

 

Siemens

 

RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation

CE1P3182en

 

Building Technologies

 

Functions

 

 

 

28 May 2009

Page 15