7.4Settings for operating mode (SET menu)

Dulcodes UV-Desinfektionsanlage

Settings

 

 

Contact: for contact operation

(Identity code, control variant: external 1:1 / external with pulse control)

Batch: for batch operation

(Identity code, control variant: external with pulse control)

Analog Manual Contact Batch

P

Analog

Manual

Contact

P

-ANALOG

-MANUAL

-CONTACT

Batch

- BATCH

 

7.4Settings for operating mode (SET menu)

NOTE

First select the operating mode in the MODE menu!

Exceptions: Timer and PROFIBUS®.

In the SET menu you can adjust various settings depending upon the selected operating mode.

The following programmable function settings menus appear in all operating modes:

Calibrate (CALIB menu)

Auxiliary frequency (AUX menu)

Flow (FLOW menu, available only if flow monitor is connected) See also section 7.5!

Further settings menus depend upon the selected operating mode.

7.4.1 Settings for ÒmanualÓ operating mode

There are no other settings menus in the overall SET menu for the “manual” operating mode apart from those described in 7.5.

7.4.2Settings for ÒanalogueÓ operating mode (ANALG menu)

In addition to those settings menus described in 7.5, there is an additional ANALG menu in the overall SET menu for the “analogue” operating mode.

The stroke rate is controlled by an analogue electrical signal via the “external control” terminal.

You can select three signal-processing methods:

0 - 20 mA: at 0 mA the S2Ca does not operate

at 20 mA the S2Ca operates at 180 strokes/min.

Between these two extremes the stroke rate is proportional to the electrical signal.

￿￿￿

P

P

Analog

mA

P

Continuous display

Set ￿￿￿￿￿

Set ￿￿￿

ProMinent®

Page 45

Page 45
Image 45