SBN TANK TYPE COMMERCIAL GAS WATER HEATER

SERVICE HANDBOOK

MODEL SBN 100-250NE

TECHNICAL DATAVENTING (Continued)

Input: 250,000 Btu/hr

 

 

 

 

 

Total Vent Height (Feet)

 

 

Vent Connector Size: 6 inches

 

6

8

10

15

20

30

50

100

 

 

Input Btuh/hr

Rise

 

Vent Connector Diameter (Inches)

 

 

250,000

1 Ft

8

8

7

7

7

6

6

6

 

 

250,000

2 Ft

7

7

7

7

6

6

6

6

 

 

250,000

3 Ft

7

7

7

7

6

6

6

6

Number

 

Combined Input

 

 

 

 

 

 

 

 

 

 

of Heaters

 

in Thousands of Btu/hr

Manifold and Common Vent Diameter (Inches)

 

2

 

500,000

 

9

9

9

8

8

7

7

7

3

 

750,000

 

12

12

10

10

10

9

8

8

4

 

1,000,000

 

14

14

12

12

10

10

9

9

MODEL SBN 100-275NE

 

 

 

 

 

 

 

 

 

 

Input: 275,000 Btu/hr

 

 

 

 

 

Total Vent Height (Feet)

 

 

Vent Connector Size:

6 inches

 

6

8

10

15

20

30

50

100

 

 

Input Btu/hr

Rise

 

Vent Connector Diameter (Inches)

 

 

275,000

1 Ft

8

8

7

7

6

6

6

6

 

 

275,000

2 Ft.

8

8

7

7

6

6

6

6

 

 

275,000

3 Ft

7

7

7

7

6

6

6

6

Number of

 

Combined Input

 

 

 

 

 

 

 

 

 

 

Heaters

 

in Thousands of Btu/hr

Manifold and Common Vent Diameter (Inches)

 

2

 

550,000

 

 

10

9

9

8

8

8

7

7

3

 

825,000

 

 

12

12

12

10

9

9

8

8

4

 

1,100,000

 

 

14

14

14

12

12

10

9

9

MODEL SBN 85-310

 

 

 

 

 

 

 

 

 

 

 

 

Input: 310,000 Btu/hr

 

 

 

 

 

Total Vent Height (Feet)

 

 

Vent Connector Size: 6 inches

 

6

8

10

15

20

30

50

100

 

 

Input Btu/hr

Rise

 

Vent Connector Diameter (Inches)

 

 

310,000

1 Ft.

 

9

8

8

8

7

7

6

6

 

 

310,000

2 Ft.

 

8

8

8

7

7

7

6

6

 

 

310,000

3 Ft.

 

8

8

8

7

7

7

6

6

Number of

 

Combined Input

 

 

 

 

 

 

 

 

 

 

Heaters

 

in Thousands of Btu/hr

 

 

Manifold & Common Vent Diameter

2

 

620,000

 

 

10

10

9

9

8

8

7

7

3

 

930,000

 

 

14

12

12

12

10

9

9

8

4

 

1,240,000

 

 

14

14

14

12

12

12

10

9

MODEL SBN 85-366NE, SBN 85-390NE

 

 

 

 

 

 

 

 

 

 

Input: 366,000, 399,000 Btu/hr

 

 

 

Total Vent Height (Feet)

 

 

Vent Connector Size:

6 inches

 

6

8

10

15

20

30

50

100

 

 

Input Btu/hr

Rise

 

Vent Connector Diameter (Inches)

 

 

366,000

1 Ft

 

9

9

9

8

8

8

8

8

 

 

399,000

1 Ft

 

10

9

9

9

8

8

8

8

 

 

366,000

2 Ft

 

9

9

8

8

8

8

8

8

 

 

399,000

2 Ft

 

9

9

9

8

8

8

8

8

 

 

366,000

3 Ft

 

9

8

8

8

8

8

8

8

 

 

399,000

3 Ft

 

9

9

8

8

8

8

8

8

Number of

 

Combined Input

 

 

 

 

 

 

 

 

 

 

Heaters

 

in Thousands of Btu/hr

 

Manifold & Common Vent Diameter (Inches)

2

 

732,000

 

 

12

10

10

9

9

9

8

8

 

 

798,000

 

 

12

12

10

10

9

9

8

8

3

 

1,098,000

 

 

14

14

14

12

12

10

9

9

 

 

1,197,000

 

 

14

14

14

12

12

10

10

9

4

 

1,464,000

 

 

16

16

14

14

14

12

12

10

 

 

1,596,000

 

 

16

16

16

14

14

12

12

10

 

 

 

 

 

 

 

 

 

 

 

 

 

Technical Training Department

17

©2003

Ashland City, Tennessee

Page 18
Image 18
State Industries STC-074 specifications Technical Dataventing